Purpose/Application

National and local safety standards and codes recognize 
the ability of air duct systems to transfer smoke, toxic 
gases, and flame from area to area. Sometimes smoke can 
be of such quantity as to be a serious hazard to life safety 
unless blowers are shut down and dampers are actuated. 
The primary purpose of duct smoke detection is to prevent 
injury, panic, and property damage by reducing the spread 
(recirculation) of smoke. The detector samples air currents 
passing through a duct and gives dependable performance 
for management of smoke and combination fire smoke 
dampers. Duct smoke detection can also serve to protect the 
air conditioning system itself from fire and smoke damage.

There are several important documents that provide guidance 
concerning the performance, application and installation of 
duct detectors:

1)  NFPA Standard 90A, 

Installation of Air Conditioning 

and Ventilating Systems

2)  NFPA Standard 92A, 

Recommended Practice for 

Smoke Control Systems

3)  NFPA Standard 72, 

National Fire Alarm Code

4)  NFPA Standard 101, 

Life Safety Code

5)  UL Standard 268A, 

Standard for Smoke Detectors for 

Duct Applications

6)  ASHRAE Handbook and Product Directory, “Fire and 

Smoke Control”

7)  System Sensor, 

Guide for Proper Use of Smoke 

Detectors in Duct Applications

.

Duct detectors are:

NOT

 a substitute for an open area smoke detector.

NOT

 a substitute for early warning detection, and

NOT

 a replacement for a building’s regular fire detection 

system.

Availability

For use with all FSD, SSFSD, SMD, SSSMD, and CFSD 
models. Not available on SMDR models.

Listings

UL 268A

Configuration

Maximum wall thickness: 6 in. (152mm) on FSD & SSFSD 

applications

 

(Consult factory for walls greater 
than 6 in. [152mm])

Actuator Location:  Must be right hand drive
 

Must be externally mounted

Detector Location:  Mounts opposite actuator side
 

Must be external

Sampling tubes longer than three feet must be supported 
on each end. Holes in duct smoke detector sampling tubes 
must face into the airflow.

Specifications

 

Type:  Photoelectric

 

Air duct velocity:  100 to 4000 fpm (.5 m/s to 

20.3 m/s)

 Operating temperature range:  32°F to 131°F (0°C to 55°C)
 

Operating humidity range:  10% to 93% R.H.

 

Operation Voltage:  24 VAC/DC or

 

  120/240 VAC

Features

•  Textured cover for convenient visual inspection.
•  The detector provides a trouble signal in the event that the 

front cover is removed.

•  Integral filter system included to reduce dust and residue 

effects on detector and housing, thereby reducing 
maintenance and servicing.

•  Terminal connections are of the strip and clamp method 

suitable for 12-18 AWG wiring.

•  Outside mounting tabs for easy connection to sleeve or 

ductwork (when detector ships loose).

DUCT SMOKE DETECTOR

DH100ACDCLP

Refer to Greenheck Installation Supplement: Part #463813 IOM-Smoke Detector Supplement

Содержание DH100ACDCLP

Страница 1: ...etectors are NOT a substitute for an open area smoke detector NOT a substitute for early warning detection and NOT a replacement for a building s regular fire detection system Availability For use with all FSD SSFSD SMD SSSMD and CFSD models Not available on SMDR models Listings UL 268A Configuration Maximum wall thickness 6 in 152mm on FSD SSFSD applications Consult factory for walls greater than...

Страница 2: ...M NBYJNVN JO TMFFWF MFOHUI PUF MM BDUVBUPST XJMM CF FYUFSOBMMZ NPVOUFE PO UIF SJHIU IBOE TJEF PG EBNQFS 4NPLF EFUFDUPS NPVOUFE FYUFSOBMMZ PO MFGU IBOE TJEF PG EBNQFS JO NJOJNVN UP BMMPX GPS SFUBJOJOH BOHMF BOE EVDU CSFBLBXBZ DPOOFDUJPO VDU SFBLBXBZ POOFDUJPO CZ PUIFST c JO Y c JO HB NJOJNVN SFUBJOJOH BOHMF c JO Y c JO HB NJOJNVN SFUBJOJOH BOHMF 4NPLF EFUFDUPS NPVOUFE FYUFSOBMMZ PO MFGU IBOE TJEF P...

Страница 3: ... 2 0A 30 VAC DC 0 6 power factor Alarm Auxiliary Contacts DPDT 10A 30 VDC 10A 250 VDC Note Alarm auxiliary contacts must switch 100 mA minimum at 5 VDC Alarm auxiliary contacts shall not be connected to initiating circuits of control panels Use the alarm initiation contact for this purpose Trouble Contacts SPDT 2 0A 30 VDC resistive Electrical Ratings Space Envelopes Typical Actuator ML series sho...

Страница 4: ...r Wiring Diagrams OPTIONAL SECOND MOTOR L2 MOTOR WHITE MOTOR L1 BLUE BLACK DH100ACDCLP DUCT DETECTOR 115 VAC RED OCI 15 5 12 11 2 1 14 13 3 4 18 8 16 17 6 7 19 20 9 10 C A B YELLOW YELLOW YELLOW YELLOW SWITCH 1 SWITCH 2 BLACK WHITE WHITE MOTOR BLACK OPTIONAL THIRD MOTOR DH100ACDCLP DUCT DETECTOR BLUE RED WHITE 24 VAC VDC WHITE 12 11 14 13 1 2 3 4 5 15 18 16 17 19 20 8 6 7 9 10 C A B 1 CONDUIT RUNS...

Страница 5: ... MOTOR L2 MOTOR WHITE MOTOR L1 BLACK ORANGE BLUE BLACK DH100ACDCLP DUCT DETECTOR 115 VAC RED RRL 15 5 12 11 2 1 14 13 3 4 18 8 16 17 6 7 19 20 9 10 C A B YELLOW YELLOW YELLOW YELLOW SWITCH 1 SWITCH 2 BLACK WHITE WHITE MOTOR BLACK OPTIONAL THIRD MOTOR DH100ACDCLP DUCT DETECTOR BLUE RED WHITE 24 VAC VDC WHITE 12 11 14 13 1 2 3 4 5 15 18 16 17 19 20 8 6 7 9 10 C A B 1 CONDUIT RUNS WHICH EXCEED 72 MUS...

Страница 6: ...82169 14 220 240 VAC BLUE 12 11 13 2 1 4 3 DH100ACDCLP DUCT DETECTOR RED WHITE 19 17 16 15 18 20 9 6 5 7 8 10 B A C L2 WHITE L1 BLUE BLACK DH100ACDCLP DUCT DETECTOR 115 VAC RED OCI 15 5 12 11 2 1 14 13 3 4 18 8 16 17 6 7 19 20 9 10 C A B YELLOW YELLOW YELLOW YELLOW SWITCH 1 SWITCH 2 DH100ACDCLP DUCT DETECTOR BLUE RED WHITE 24 VAC VDC WHITE 12 11 14 13 1 2 3 4 5 15 18 16 17 19 20 8 6 7 9 10 C A B R...

Страница 7: ...IRES SHOULD THEN BE LABELED WITH A BLUE WIRE MARKER 382169 B C A 9 10 6 7 4 5 2 3 1 8 19 20 17 14 15 16 12 13 11 18 WHITE RED BLUE 220 240 VAC DH100ACDCLP DUCT DETECTOR RRL OCI W EP Switch L2 WHITE L1 BLACK ORANGE BLUE BLACK DH100ACDCLP DUCT DETECTOR 115 VAC RED RRL 15 5 12 11 2 1 14 13 3 4 18 8 16 17 6 7 19 20 9 10 C A B DH100ACDCLP DUCT DETECTOR BLUE RED WHITE 24 VAC VDC WHITE 12 11 14 13 1 2 3 ...

Страница 8: ... E P SWITCH RED WHITE E P SWITCH RED BLACK BLACK 1 CONDUIT RUNS WHICH EXCEED 72 MUST HAVE GREEN GROUND WIRE 2 FLEX CONDUIT MUST BE SECURED WITH A CONDUIT CLAMP 458296 WITHIN 12 OF CONDUIT TERMINATION AT THE HANDI BOX OR ACTUATOR CONDUIT RUNS MUST ALSO BE SECURED ALONG SLEEVE AT A MAXIMUM OF 24 ON CENTER THE OCI WIRES MUST BE CHECKED TO VERIFY WHICH SET INDICATES THE CLOSED POSITION OF DAMPER THIS ...

Отзывы: