background image

These installation instructions apply to 3 hour rated ceiling radiation dampers mounted in a ceiling with supports 
from 1) a ceiling grid system, 2) ductwork above, or 3) structure above. Each type of damper support system is 
described with damper being mounted in conjunction with various air devices. 

1.    

Application:

.PEFM$3%JTB6-MBCFMFE

ceiling radiation damper. When installed as shown, 
they provide appropriate protection for air inlet 
or outlet penetrations in the ceiling membrane of 
floor/ceiling and roof/ceiling assemblies with fire 
resistance ratings of up to 3 hours. Use of these 

6-MBCFMFEDFJMJOHEBNQFSTFMJNJOBUFTUIFOFFEUP

use “hinged door” type dampers or other alternate 
protection methods for specific floor/ceiling 

BOESPPGDFJMJOHEFTJHOTTIPXOJOUIF6-'*3&

RESISTANCE DIRECTORY (FRD).

2. 

 System Components:

 All system components 

(ducts, duct drops, hanger wires, sleeves, and 
diffuser pan) must be constructed of steel. The 
diffuser core may be non-ferrous. Grilles may 
be non-metallic. Flexible duct (if used) must be 

$MBTT*PS$MBTT0UZQFCFBSJOHUIF6-MJTUJOH
NBSL.BYJNVNMFOHUIPGGMFYEVDUTIBMMOPU

exceed 14 feet (4.27 m). The installations and 
air devices shown in these instructions illustrate 
general arrangement only. Installations must also 
incorporate any specific requirements in the FRD. 
Note that both “Design information - General” and 
individual ceiling/floor or ceiling/roof design listings 
apply.

3.  

Ceiling Penetrations:

 Ceiling penetration should 

be located within ceiling tiles or panels without 
necessitating cuts in the ceiling suspension main 
runners or cross tees. If required, a maximum 
of one runner or cross tee may be cut to enable 
proper damper location and installation. Each cut 

 Ceiling Radiation Damper Application

end shall be supported by a minimum 12 SWG 
vertical hanger wire. A 

½ 

in. (13mm) clearance must 

be maintained between the air inlet/outlet and the 
cut end of the runner or cross tee.

4.  

Connections:

 Connections must be made using #8 

sheet metal screws, 3/16 in. (4.7mm) tubular steel 
rivets, tack or spot welds. Use a minimum of three 
equally spaced connections. Space fasteners a 
maximum of 6 in. (152mm) apart. All screws or rivet 
attachments shall be placed a minimum of 3/16 
in. (4.7mm) from the edge of the damper frame, 
duct drop, diffuser, or grille frame. When making 
connections, the ceiling radiation damper may slide 
over the neck or inside the neck of the diffuser, 
grille, or inlet/outlet device. Important: Connections 
to damper frame must not interfere with damper 
blade operation.

5.  

Thermal Blanket:

 In those installations where the 

opening in the ceiling membrane is larger than 
the ceiling damper (more than 1 in. (25mm) in any 

EJNFOTJPOB5IFSNBM*OTVMBUJOH#MBOLFU .PEFM5#

or QB) must be installed by laying over the exposed 
surface of the air inlet or outlet device. The Thermal 
Blanket rests upon and protects exposed portions 
of the air device and may fit inside adjacent Tee 
Bars (if any).

6.  

Thermostat:

 The CRD-501 is shipped from the 

factory with the blades closed. The CRD-501 is 

FRVJQQFEXJUI33- 3FTFUUBCMF-JOL

Dampers Supported By A Ceiling Grid System

Exposed Tee Bar ceiling grid systems often use 

-BZ*OwTUZMFBJSJOMFUTBOEPVUMFUT8JUIBUUFOUJPOUP

the following requirements, the ceiling grid system 
provides all required support for installation of “

-BZ*Ow

style ceiling dampers and air inlets and/or outlets.

Ceiling openings up to a 24 in. x 24 in. (576 in.

2

(610mm x 610mm [.371 m 

]) 

maximum are allowable. 

.BYJNVNTJ[FMJNJUTPGFBDIJOEJWJEVBMDFJMJOHEBNQFS

model must be observed.

The four corners of the grid module containing the 
air device (or the midpoint of the adjacent cross-
tees) shall be directly supported from the structural 

members of the floor or roof by 12 SWG minimum 
vertical hanger wires. When the duct extends over 
the intersections of the grid members, 16 ga. x 1

½ 

in. 

(1.5mm x 38mm) steel channels with 9/16 in. (14mm)
minimum flanges shall be used to ensure that the 
grid is supported from structural members by 12 

48(NJOJNVNIBOHFSXJSFT"MM6-$MBTTJGJFEDFJMJOH

assemblies require lay-in ceiling panels be cut to fill the 
remainder of hole openings larger than 24 in. x 24 in. 
(610mm x 610mm) and shall provide a minimum of 3/8 
in. (9.5mm) bearing on the ceiling grid members.

Содержание CRD-501

Страница 1: ...ther is highly recommended Do not store at temperatures in excess of 100 F 38 C Safety Caution Electrical input may be needed for this equipment This work should be performed by a qualified electricia...

Страница 2: ...teel rivets tack or spot welds Use a minimum of three equally spaced connections Space fasteners a maximum of 6 in 152mm apart All screws or rivet attachments shall be placed a minimum of 3 16 in 4 7m...

Страница 3: ...be fastened to the diffuser neck with a steel clamp or 16 SWG minimum wire NOTE 1 The flexible air duct shall not rest on the back surface of the ceiling grid or panels provide a minimum of 4 in 102m...

Страница 4: ...MJOH SBEJBUJPO EBNQFS BJS EFWJDF neck and steel duct drop see page 2 paragraph 4 may be satisfied in as follows 1 Ceiling radiation damper may be connected directly to the air device neck and then the...

Страница 5: ...BSBHSBQI t POOFDUJPO PG DFJMJOH SBEJBUJPO EBNQFS BJS EFWJDF neck and steel duct drop see page 2 paragraph 4 may be satisfied as follows 1 Ceiling radiation damper may be connected directly to the air...

Страница 6: ...JBUJPO damper See Page 2 Paragraph 4 t POOFDUJPO PG DFJMJOH SBEJBUJPO EBNQFS BJS EFWJDF neck and steel duct drop See Page 2 Paragraph 4 may be satisfied as follows 1 Ceiling radiation damper may be co...

Страница 7: ...n diameter 305mm ceiling radiation damper could have a maximum ceiling membrane opening of 13 in 330mm t Connection of ceiling radiation damper and air device neck See Page 2 Paragraph 4 may be satisf...

Страница 8: ...directly to the air device neck and supported by hanger straps See Detail B Figure 8 3 Ceiling radiation damper may be connected directly to the air device neck and supported by direct suspension wit...

Страница 9: ...pe Single Pole double throw Electrical Capacity 10 Amps 1 3 hp 120 or 240 Vac 1 2 Amp 125 Vdc 1 4 Amp 250 Vdc 5 Amps 120 Vac L lamp load 1 0 Amps 24 Vac 1 5 Amps 24 Vdc Temperature Limit 165 F standar...

Отзывы: