background image

H*

W*

APPLICATION

Model FSD-211 is a combination fire smoke damper with 3V style 

blades. The FSD-211 has been qualified to 2000 fpm (10.2 m/s) and 

4 in. wg (1 kPa) for operation and dynamic closure in emergency fire 

smoke situations. Model FSD-211 may be installed vertically (with 

blades running horizontal) or horizontally and is rated for airflow and 

leakage in either direction.

RATINgs

UL 555 Fi re Resistance Rating

 

Fire Rating:

 

1

1

2

 

Hours 

 

Dynamic Closure Rating

: Actual ratings are size dependent 

 

Maximum Velocity:

 

2000 fpm (10.2 m/s) 

 

Maximum Pressure:

 

4 in. wg (1 kPa) 

 

Maximum Temperature:

 350ºF (177°C) -- Depending on 

 

 

actuator

UL 555S Leakage Rating

 

Leakage Class:

 

 

Operational Rating: 

 

Actual ratings are actuator dependent 

 

Maximum Velocity

2000 fpm (10.2 m/s) 

 

Maximum Pressure:

 

4 in. wg (1 kPa) 

 

Maximum Temperature:

 350ºF (177°C) - Depending on 

 

 

actuator

sTANdARd CONsTRuCTION

 

Frame:

  

5 in. x 1 in. (127mm x 25mm) 

 

 

galvanized steel hat channel with 

 

 

reinforced corners. A low profile head 

 

 

and sill are used on sizes less than 

 

 

17 in. (432mm) high to maximize free 

 

 

area and performance. 

 

Blades: 

 

16 ga. (1.5mm) galvanized steel, 

 

 

reinforced with 3 longitudinal 

 

 

structurally designed vee’s. 

 

Seals:

 

Extruded silicone rubber blade seals 

 

Jamb Seals:

 

Flexible stainless steel jamb seals 

 

Linkage:

 

Concealed in jamb. 

 

Closure Device:

 

UL listed 165°F (74°C) RRL 

 

Axles:

 

1

2

 in. (13mm) dia. plated steel 

 

Bearings:

 

Bronze sleeve type

sIze LImITATIONs:

 

Minimum Size:

 

8 in. W x 6 in. H (203mm W x 152mm H) 

 

Maximum Size: 

 

Single Section: 32 in. W x 50 in. H 

 

 

(813mm W x 1270mm H) 

 

 

36 in. W x 48 in. H 

 

 

(914mm x 1219mm) 

 

 

Multiple Section:  

 

 

Horizontal: 144 in. W x 96 in. H 

 

 

(3658mm W x 2438mm H) 

 

 

Vertical:  128 in. W x 100 in. H 

 

 

(3251mm W x 2540mm H)

OPTIONAL FeATuRes:

• RRL/OCI (Open closed indication switches)

 

• Electric or pneumatic actuators

 

• POC retaining angles

 

• Smoke detectors

 

• Momentary switch

 

• Pneumatic Relief Valve (PRV)

 

• Security bars

 

• TOR (remote override of 165ºF (74°C) or 212ºF (100°C) closure

 

  allows damper to perform smoke management functions during a 

  fire emergency) 

• 165ºF (74°C), 212°F (100°C), 250ºF (121°C), and 350ºF (177°C)

 

  RRL's available. 

• Sealed transitions and sleeves

model Fsd-211

Combination 

FIRe smOKe dAmPeRs

 

Steel 3-V Blades

UL 555S Leakage Class I

UL555 1

1

2

 Hour Fire Resistance Rating

*W&H dimensions furnished approximately ¼in. (6mm) undersize. 
(Add sleeve thickness for overall sleeved damper dimension) 
Right hand drive is shown. Left hand drive is available upon request.

LH

RH

Model FSD-211 meets the requirements for fire 

dampers, smoke dampers and combination fire 

smoke dampers established by:

National Fire Protection Association

NFPA Standards 80, 90A, 92A, 92B, 101 & 105

IBC  International Building Codes
ICBO  uniform Building Codes  
CsFm California state Fire marshal 

  Fire Damper Listing (#3225-0981:103)
  Leakage (Smoke) Damper Listing (#3230-0981:104)

New York City 

(MEA listing #260-91-M)

“uL CLAssIFIed (see complete marking on 

product)”

“uL CLAssIFIed to Canadian safety standards 

(see complete marking on product)”

 

Standard 555 & 555S (Listing #R13317)

R

Greenheck Fan Corporation certifies that the 
model FSD-211 shown herein is licensed to bear 
the AMCA Seal. The ratings shown are based on 
tests and procedures performed in accordance 
with AMCA Publication 511 and comply with 
the requirements of the AMCA Certified Ratings 
Programs. The AMCA Certified Ratings Seal 
applies to air performance ratings only. 

Installation installations available at www.greenheck.com

Содержание Combination Fire Smoke Damper FSD-211

Страница 1: ...3658mm W x 2438mm H Vertical 128 in W x 100 in H 3251mm W x 2540mm H Optional Features RRL OCI Open closed indication switches Electric or pneumatic actuators POC retaining angles Smoke detectors Mome...

Страница 2: ...tem AMCA Test Figures Figure 5 3 Illustrates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by st...

Страница 3: ...reDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 04 500 0 02 500 0 01 500 0 01 1000 0 14 1000 0 07 1000 0 04 1000 0 06 1500 0 31 1500...

Страница 4: ...0 0 48 3500 0 33 3500 0 53 4000 1 44 4000 0 63 4000 0 42 4000 0 70 12in x12in 305mm x 305mm 24in x24in 610mm x 610mm 36in x36in 914mm x 914mm 12in x48in 305mm x 1219mm Velocity fpm Pressure Drop in wg...

Страница 5: ...m PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 06 500 0 03 500 0 03 500 0 03 1000 0 22 1000 0 14 1000 0 12 1000 0 13 1500 0 50 1500 0 31 1500 0 26 1500 0 30...

Страница 6: ...her locations within a range of 6 in 152mm to 12 in 305mm for the A dimension Application Data 53 8 in 5 in Right hand drive is shown Left hand drive available upon request LH RH A Sleeve Length Varie...

Страница 7: ...be completely symmetrical relative to their axle pivot point presenting identical resistance to airflow in either direction or pressure on either side of the damper The Damper Manufacturer s submitta...

Отзывы: