Greenheck ASSURE-120S-S1 Скачать руководство пользователя страница 32

Troubleshooting

Table 16. Troubleshooting

Symptom

Cause

Solution

Poor airflow(s)

Mesh on outside hoods plugged

Filters plugged

Core obstructed

House grilles closed or blocked

Dampers closed (if installed)

Poor power supply at site

Ductwork is restricting ERV

Improper speed control setting

ERV airflow improperly balanced

Clean exterior hoods or vents

Remove and clean both filter and core

If unit is equipped with MERV 13 filters,
replace every 3 months.

Check and open grilles

Open and adjust dampers

Have electrician check supply voltage at
house

Check duct installation

Increase the speed of the ERV

Have contractor balance the ERV

Supply air feels cold

Poor location of supply grilles

Airflow may irritate occupants

Outdoor temperature extremely cold

Locate the grilles high on the walls or under
the baseboards

Install ceiling mounted diffuser or grilles so as
not to direct airflow onto occupants (e.g. over
a couch)

Turn down the ERV supply speed

A small duct heater (1kw) could be used to
temper the supply air

Placement of furniture or closed doors
restricting movement of air in home; consider
rearranging

If supply air is ducted into furnace return, the
furnace fan may need to run continuously to
distribute ventilation air comfortably

Dehumidistat is not operating

Outdoor temperature is above 59

º

F (15

º

C)

Improper low−voltage connection

External low voltage is shorted out by a staple
or nail

Check dehumidistat setting; it may be OFF

Dehumidistat is functioning normally (see
“Dehumidistat Disable” on page 10)

Check that the correct terminals have been
used

Check external wiring for a short

Set the dehumidistat at the desired level

Humidity levels are too high; condensation is 
appearing on windows

Dehumidistat set too high

ERV unit is undersized to handle a hot tub,
indoor pool, etc. (Occupant Lifestyle)

Moisture coming into the home from an non-
vented or non-heated crawl space

Moisture remaining in washroom and/or
kitchen areas

Condensation seems to form in the spring and
fall seasons

ERV is set at too low a speed

Set dehumidistat at lower level

Cover pool or hot tub when not in use

Avoid hanging clothes to dry indoors, storing
wood indoors, and venting dryer inside

Vent crawl space and place a vapor barrier on
the floor of the crawl space

Ducts from washroom should be sized to
remove moist air as effectively as possible;
use of a bathroom fan for short periods will
remove additional moisture

On humid days, as seasons change, some
condensation may appear but the home’s air
quality will remain high with some ERV use

Increase speed of ERV

Humidity levels are too low

Dehumidistat control set too low

Blower speed of ERV is too high

Occupant lifestyle issue

ERV airflows may be improperly balanced

Set dehumidistat at higher level.

Decrease ERV blower speed

Humidity may have to be added through use
of humidifiers

Have a contractor balance ERV airflows

ERV units and/or ducts frosting up

ERV air flows are improperly balanced

Malfunction of the ERV defrost system

NOTE: Minimal frost build-up is expected on
cores before unit initiates defrost cycle.

Have HVAC contractor balance the ERV
airflows

Ensure damper defrost is operating during
self−test

Condensation or ice build−up in insulated duct to 
the outside

Incomplete vapor barrier around insulated
duct

Hole or tear in outer duct covering

Tape and seal all joints

Tape any holes or tears made in the outer
duct covering

Ensure that the vapor barrier is complete
sealed

Water in the bottom of the ERV unit

Drain pans plugged

Improper connection of ERV drain lines

ERV is not level

Drain lines obstructed

ERV heat exchange core is not properly
installed

Look for kinks in the drain line

Check water drain connections

Make sure water drains properly from pan(s)

Residential Energy Recovery Ventilators

32

®

Содержание ASSURE-120S-S1

Страница 1: ...wo Speed Switch with Humidity Sensor 435245 11 PrecisionSYNC Control 435244 12 20 40 60 Minute Timer 435247 13 20 40 60 Minute Wireless Timer 435248 13 Wireless Repeater 435249 13 Overview of Installa...

Страница 2: ...d for ceiling mounting in single family or multi unit residential buildings Fan defrost unit with no balancing or drains required SYNC110 SYNC 110SE S1 50 130 CFM compact high efficiency Energy Recove...

Страница 3: ...r fan operation to be initiated For example the ERV is set to Continuous Ventilation Operation Mode at speed 0 Thermistor This is the temperature sensor that measures electrical resistance as outdoor...

Страница 4: ...78 49 CFM 23 L s 75 64 CFM 30 L s 87 64 CFM 30 L s 81 Sensible Recovery Efficiency 32 F 0 C 49 CFM 23 L s 69 49 CFM 23 L s 72 64 CFM 30 L s 84 64 CFM 30 L s 77 Adjusted Sensible Recovery Efficiency 13...

Страница 5: ...filter is installed for the first time airflow will need to be balanced Condensate Drain Connections Spouts qty 2 1 2 o d Drain Tee qty 1 1 2 o d No No No Yes optional use Drain Plug Included No No N...

Страница 6: ...7 46 42 20 102 48 215 101 0 6 150 92 43 89 42 202 95 0 7 175 87 41 76 36 192 90 0 8 200 80 38 63 30 177 83 0 9 225 72 34 49 23 165 78 1 0 250 34 16 155 73 Speed 3 Medium IN WG PA CFM L s CFM L s CFM L...

Страница 7: ...IDE VIEW 10 in 254 mm 22 in 559 mm 6 in 152 mm Collars Collar mounted balancing ports Core Motorized Impellers Filters Stale Air to Outside Airflow Fresh Air from Outside Stale Air from Inside Fresh A...

Страница 8: ...SYNC 270TCE S1 During defrost a motor driven damper door mechanism closes off the supply air from outside allowing exhaust air to recirculate through the unit s core During the defrost portion of the...

Страница 9: ...0 X 0 03 4 1 X 7 5 97 5 Table Method Example a 2000 square foot building with 4 bedrooms from Section 4 1 1 Table 4 1a a quick reference table predicts 98 cfm The following table complies with ASHRAE...

Страница 10: ...vious setting It is recommended to operate the ERV for the first few days without use of the dehumidistat function to observe if a further dehumidification effect will be required The dehumidistat ope...

Страница 11: ...amper defrost models Table 7 Two Speed Switch with Humidity Sensor Settings Settings Icon Description Turning on the Control Press and release the ON OFF button The light above will illuminate Setting...

Страница 12: ...time interval selected When the timer runs out the unit will return to its previous operating speed Setting the Mode of Operation There are five modes of operation available with the PrecisionSYNC Co...

Страница 13: ...have an estimated range of 40 feet 12 meters with no obstructions To increase the range of the timer a Wireless Repeater may be used Multiple timers can be paired to a single control They are designed...

Страница 14: ...gth approximately 12 inches 300 mm of non metallic flexible duct should be connected between the ERV and the supply exhaust duct system to avoid possible noise transfer through the duct system All duc...

Страница 15: ...tion may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for acceptance Installation Methods Simplified Return Return Figure 13 S...

Страница 16: ...ler Furnace Blower on page 24 The duct configuration may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for acceptance Installat...

Страница 17: ...igures KEY POINTS The ERV unit must be balanced The duct configuration may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for ac...

Страница 18: ...or during adjustment of the straps 4 Level the unit from left to right and front to back Adjust the unit down by lifting up on the buckles Adjust the unit up by pulling down vertically on the hand loo...

Страница 19: ...trated in Figure 23 Drain Holes and P Trap 1 Cut two lengths of hose and connect each piece to an end of the T fitting then connect the other ends to the two drain spouts 2 Position the T fitting to p...

Страница 20: ...aust The pressure drop airflow charts should be referred to when matching the Dual Intake and Exhaust Hood to the ERV The Dual Intake and Exhaust Hood Kit is compatible with 5 or 6 diameter duct ERV D...

Страница 21: ...through the opening in the wall 8 Connect red green and yellow to the wiring terminals located on the back plate Figure 29 Boxes D E or F 9 Attach the back plate to the wall using two supplied screws...

Страница 22: ...If pairing was not successful you now must return to step 1 to restart the pairing process 6 Press the button on the control to exit pairing mode when wireless timers have been successfully paired To...

Страница 23: ...e Wireless Timer and Control To pair additional Wireless Repeater 435249 with the same control repeat steps 1 5 until all Wireless Repeaters 435249 have been paired When installed in its permanent loc...

Страница 24: ...Only The ERV is compatible with two wire dry contact third party mechanical timers This may be useful for retrofit situations where only two wires are available for the timer Install the two wire time...

Страница 25: ...setting the control to ON and selecting speed 0 Timers will initiate high speed ventilation when activated CAUTION Building codes in some areas require fully off functionality Check with your local b...

Страница 26: ...nit Wiring Diagrams Applicable Unit ASSURE 120S S1 Applicable Unit SYNC 110SE S1 Figure 37 ASSURE 120S S1 Wiring Diagram Figure 38 ERV 110E S1 Wiring Diagram Residential Energy Recovery Ventilators 26...

Страница 27: ...otor Damper Defrost Units Only BLUE BLACK WHITE WHITE Door Switch Note If any of the original wires supplied must be replaced use only TEW certified wire Important Control wiring low voltage communica...

Страница 28: ...Defrost cycle enabled Dip 2 Null Switch 2 Dip 1 On R2000 Defrost cycle disabled Dip 1 Off R2000 Defrost cycle enabled Dip 2 Null Switch 1 Auto balance Unit Selection Switch 1 Auto balance Unit Select...

Страница 29: ...Gauge A digital manometer is a suitable instrument for the balancing of airflows Gauge Attachments When sampling an airflow various attachments are available for use on a digital manometer The illust...

Страница 30: ...Air to Inside stream 4 Review the readings and damper down the duct with the highest duct velocity pressure Repeat Steps 2 and 3 until both ducts show identical readings Upon completion of balancing...

Страница 31: ...et value CFM Pause until the airflow values CFM have stabilized Airflow values CFM increase and decrease in increments of 5 CFM CFM fluctuations of 10 CFM from target is acceptable A Balance Indicator...

Страница 32: ...tc Occupant Lifestyle Moisture coming into the home from an non vented or non heated crawl space Moisture remaining in washroom and or kitchen areas Condensation seems to form in the spring and fall s...

Страница 33: ...d any debris 4 Install clean core as follows a Install the bottom flange of the core guide into the bottom H channel approximately 1 4 6 mm b Install the left or right side flange of the core guide ap...

Страница 34: ...attached firmly Seal and tape insulation and moisture barrier not applicable for SYNC 270TCE S1 A capable HVAC service company will best perform this procedure Homeowner Maintenance Information conti...

Страница 35: ...al and Commercial Fans provides additional safety information This publication can be obtained from AMCA International Inc at www amca org As a result of our commitment to continuous improvement Green...

Отзывы: