NOTE: Wireless timers can only be used with wall mounted Two-Speed Switch or PrecisionSYNC Control (435244).

The wireless timers may be installed onto a flush mounted electrical switch 

box or it may be surface mounted onto a wall. Multiple wireless timers 

(maximum six timers) may be installed with ventilation system.

To increase the range of a wireless timer, a Wireless Repeater should be 

used.

Pairing

1.  Turn on the main wall control by pressing the ON/OFF button            and 

remove the battery from 20/40/60 Minute Wireless Timer.

2.  Pairing PrecisionSYNC Control (435244): Press the left and right buttons 

simultaneously on the control        and RESET buttons. The screen will 
go blank and the wireless symbol          appear flashing on the bottom 
right of the display. This indicates that the control is now in pairing mode 
(Figure 30, Box D).

3.  Pairing 20/40/60 Minute Wireless Timer (435248) with Two-Speed Switch 

with Humidity Sensor (435245) and  Two-Speed Switch with Intermittent 
Mode (435246): Press the left and right buttons simultaneously on the 
control       and        buttons). The bottom row of three LEDs will begin 
flashing. This indicates that the main control is now in pairing mode 
(Figure 30, Box E).

4.  Keep the timer within 16” (406 mm) of the control when pairing.
5.  Install the battery in the 20/40/60 Minute Wireless Timer. All four lights 

on the timer will immediately flash five times, then only the red battery 
light will remain on for approximately 12 seconds after which the 40 light 
flashes. 20, 40, 60 lights will flash until paired or will stop if not paired 
within 12 seconds. If pairing was not successful you now must return to 
step 1 to restart the pairing process.

6.  Press the         button on the control to exit pairing mode when wireless 

timers have been successfully paired.

To pair additional wireless timers with the same wall control, or if pairing was 
not successful, repeat steps 1-6.

When paired, the wireless timers can be moved and installed elsewhere.

Estimated range of the wireless timer is 40’ with no obstructions. A Wireless Repeater may be installed to increase the range of the 
20/40/60 Minute Wireless Timer.

For Two-Speed Switch with Humidity Sensor (435245) and Two-Speed Switch with Intermittent Mode (435246): To test if the pairing 
was successful, ensure the unit is in low speed then press the button on the 20/40/60 Minute Wireless Timer and listen for the ERV to 
initiate HIGH fan speed ventilation.

For PrecisionSYNC Control (435244): To test if the pairing was successful press the button on the 20/40/60 Minute Wireless Timer 

and look for the Timer           icon to display on the LED screen next to the fan speed.

Installation and Operation of 20/40/60 Minute Wireless Timer (435248)

BOX A

BOX B

1/8” (3 mm) hole

for screw and anchor

1/8” (3 mm) hole

for screw and anchor

BOX C 

(ALTERNATE WALL MOUNT)

Digital 5 Speed / 5 Mode Control

1/8” (3 mm) hole

for screw and anchor

Break off tab

1/8” (3 mm) hole

for screw and anchor

Break off tab

BOX D

BOX E

2 Speed

Ventilation

Control

Press Simultaneously to

Initiate Pairing Mode

BOX F

2#

TOP

Back Plate

Face Plate

2#

TOP

Press Simultaneously to

Initiate Pairing Mode

Removable

Backplate

 

20/40/60 Minute

Status Lights 

 

Select Button initiates

high speed ventilation

for 20, 40 or 60 min. 

 

Wireless 20/40/60 Minute Timer

Figure 30. Installation of Timer

Residential Energy Recovery Ventilators

22

®

Содержание ASSURE-120S-S1

Страница 1: ...wo Speed Switch with Humidity Sensor 435245 11 PrecisionSYNC Control 435244 12 20 40 60 Minute Timer 435247 13 20 40 60 Minute Wireless Timer 435248 13 Wireless Repeater 435249 13 Overview of Installa...

Страница 2: ...d for ceiling mounting in single family or multi unit residential buildings Fan defrost unit with no balancing or drains required SYNC110 SYNC 110SE S1 50 130 CFM compact high efficiency Energy Recove...

Страница 3: ...r fan operation to be initiated For example the ERV is set to Continuous Ventilation Operation Mode at speed 0 Thermistor This is the temperature sensor that measures electrical resistance as outdoor...

Страница 4: ...78 49 CFM 23 L s 75 64 CFM 30 L s 87 64 CFM 30 L s 81 Sensible Recovery Efficiency 32 F 0 C 49 CFM 23 L s 69 49 CFM 23 L s 72 64 CFM 30 L s 84 64 CFM 30 L s 77 Adjusted Sensible Recovery Efficiency 13...

Страница 5: ...filter is installed for the first time airflow will need to be balanced Condensate Drain Connections Spouts qty 2 1 2 o d Drain Tee qty 1 1 2 o d No No No Yes optional use Drain Plug Included No No N...

Страница 6: ...7 46 42 20 102 48 215 101 0 6 150 92 43 89 42 202 95 0 7 175 87 41 76 36 192 90 0 8 200 80 38 63 30 177 83 0 9 225 72 34 49 23 165 78 1 0 250 34 16 155 73 Speed 3 Medium IN WG PA CFM L s CFM L s CFM L...

Страница 7: ...IDE VIEW 10 in 254 mm 22 in 559 mm 6 in 152 mm Collars Collar mounted balancing ports Core Motorized Impellers Filters Stale Air to Outside Airflow Fresh Air from Outside Stale Air from Inside Fresh A...

Страница 8: ...SYNC 270TCE S1 During defrost a motor driven damper door mechanism closes off the supply air from outside allowing exhaust air to recirculate through the unit s core During the defrost portion of the...

Страница 9: ...0 X 0 03 4 1 X 7 5 97 5 Table Method Example a 2000 square foot building with 4 bedrooms from Section 4 1 1 Table 4 1a a quick reference table predicts 98 cfm The following table complies with ASHRAE...

Страница 10: ...vious setting It is recommended to operate the ERV for the first few days without use of the dehumidistat function to observe if a further dehumidification effect will be required The dehumidistat ope...

Страница 11: ...amper defrost models Table 7 Two Speed Switch with Humidity Sensor Settings Settings Icon Description Turning on the Control Press and release the ON OFF button The light above will illuminate Setting...

Страница 12: ...time interval selected When the timer runs out the unit will return to its previous operating speed Setting the Mode of Operation There are five modes of operation available with the PrecisionSYNC Co...

Страница 13: ...have an estimated range of 40 feet 12 meters with no obstructions To increase the range of the timer a Wireless Repeater may be used Multiple timers can be paired to a single control They are designed...

Страница 14: ...gth approximately 12 inches 300 mm of non metallic flexible duct should be connected between the ERV and the supply exhaust duct system to avoid possible noise transfer through the duct system All duc...

Страница 15: ...tion may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for acceptance Installation Methods Simplified Return Return Figure 13 S...

Страница 16: ...ler Furnace Blower on page 24 The duct configuration may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for acceptance Installat...

Страница 17: ...igures KEY POINTS The ERV unit must be balanced The duct configuration may change depending on the ERV model See specifications for your unit Check local codes and authority having jurisdiction for ac...

Страница 18: ...or during adjustment of the straps 4 Level the unit from left to right and front to back Adjust the unit down by lifting up on the buckles Adjust the unit up by pulling down vertically on the hand loo...

Страница 19: ...trated in Figure 23 Drain Holes and P Trap 1 Cut two lengths of hose and connect each piece to an end of the T fitting then connect the other ends to the two drain spouts 2 Position the T fitting to p...

Страница 20: ...aust The pressure drop airflow charts should be referred to when matching the Dual Intake and Exhaust Hood to the ERV The Dual Intake and Exhaust Hood Kit is compatible with 5 or 6 diameter duct ERV D...

Страница 21: ...through the opening in the wall 8 Connect red green and yellow to the wiring terminals located on the back plate Figure 29 Boxes D E or F 9 Attach the back plate to the wall using two supplied screws...

Страница 22: ...If pairing was not successful you now must return to step 1 to restart the pairing process 6 Press the button on the control to exit pairing mode when wireless timers have been successfully paired To...

Страница 23: ...e Wireless Timer and Control To pair additional Wireless Repeater 435249 with the same control repeat steps 1 5 until all Wireless Repeaters 435249 have been paired When installed in its permanent loc...

Страница 24: ...Only The ERV is compatible with two wire dry contact third party mechanical timers This may be useful for retrofit situations where only two wires are available for the timer Install the two wire time...

Страница 25: ...setting the control to ON and selecting speed 0 Timers will initiate high speed ventilation when activated CAUTION Building codes in some areas require fully off functionality Check with your local b...

Страница 26: ...nit Wiring Diagrams Applicable Unit ASSURE 120S S1 Applicable Unit SYNC 110SE S1 Figure 37 ASSURE 120S S1 Wiring Diagram Figure 38 ERV 110E S1 Wiring Diagram Residential Energy Recovery Ventilators 26...

Страница 27: ...otor Damper Defrost Units Only BLUE BLACK WHITE WHITE Door Switch Note If any of the original wires supplied must be replaced use only TEW certified wire Important Control wiring low voltage communica...

Страница 28: ...Defrost cycle enabled Dip 2 Null Switch 2 Dip 1 On R2000 Defrost cycle disabled Dip 1 Off R2000 Defrost cycle enabled Dip 2 Null Switch 1 Auto balance Unit Selection Switch 1 Auto balance Unit Select...

Страница 29: ...Gauge A digital manometer is a suitable instrument for the balancing of airflows Gauge Attachments When sampling an airflow various attachments are available for use on a digital manometer The illust...

Страница 30: ...Air to Inside stream 4 Review the readings and damper down the duct with the highest duct velocity pressure Repeat Steps 2 and 3 until both ducts show identical readings Upon completion of balancing...

Страница 31: ...et value CFM Pause until the airflow values CFM have stabilized Airflow values CFM increase and decrease in increments of 5 CFM CFM fluctuations of 10 CFM from target is acceptable A Balance Indicator...

Страница 32: ...tc Occupant Lifestyle Moisture coming into the home from an non vented or non heated crawl space Moisture remaining in washroom and or kitchen areas Condensation seems to form in the spring and fall s...

Страница 33: ...d any debris 4 Install clean core as follows a Install the bottom flange of the core guide into the bottom H channel approximately 1 4 6 mm b Install the left or right side flange of the core guide ap...

Страница 34: ...attached firmly Seal and tape insulation and moisture barrier not applicable for SYNC 270TCE S1 A capable HVAC service company will best perform this procedure Homeowner Maintenance Information conti...

Страница 35: ...al and Commercial Fans provides additional safety information This publication can be obtained from AMCA International Inc at www amca org As a result of our commitment to continuous improvement Green...

Отзывы: