Sidewall Propeller Fans

4

®

•  Check chart below for correct wall opening 

dimensions.

•  Check motor voltage and amperage rating for 

compatibility with electrical supply. Supply wiring 
must be properly fused and conform to local and 
national codes.

•  Motor load amperage must be checked and 

compared to nameplate rating to avoid serious 
damage to motor when speed is increased.

Wall Opening Requirements

Wall opening size and propeller-to-damper distance 
are two important dimensions for fan installation. Fans 
mounted to the wall require a different wall opening 
(W.O.) size than those mounted in collars or wall 
housings. Propeller-to-damper distance (M) is important 
to reduce turbulence and damper flutter which may lead 
to premature damper failure.

Pre-Installation Checks

Fan

Size

Damper

Size 

Square

Recommended Wall Opening 

(W.O.) Square

M

Minimum

Figure 1 

Figure 2

500 (20)

559 (22)

692 (27-1/4) 

572 (

22-1/2)

305 (

12)

630 (24)

660 (26)

857 (33-3/4) 

673 (

26-1/2)

330 (13)

800 (30)

813 (32)

1010 (39-3/4) 826 (32-1/2)  330 (13)

900 (36)

965 (38)

1162 (45-3/4) 978 (38-1/2)

356 (14)

All dimensions given in millimeters 

(inches)

. Filters are 2 inch 

(51 mm)

 nominal thickness. Above filter sizes are actual dimensions.

Figure 2 - Direct to Wall Installation

Figure 1 - Wall Housing Installation

M

W.O.

W.O.

W.O.

M

W.O.

W.O.

W.O.

Figure 1 

shows the wall opening (W.O.) required for 

installations with either a wall housing or collar.

Figure 2

 shows the recommended wall opening (W.O.) 

and the minimum distance (M) suggested between the 
fan and damper for direct to wall installations.

Содержание AER-M

Страница 1: ...quately grounded 4 Do not spin fan propeller faster than max cataloged fan RPM Adjustments to fan speed significantly affects motor load If the fan RPM is changed the motor current should be checked t...

Страница 2: ...build up Leave coverings loose to permit air circulation and to allow for periodic inspection The unit should be stored at least 3 1 2 inch 89 mm off the floor on wooden blocks covered with moisture...

Страница 3: ...it be operated in a completely level position For further details on safety practices involving industrial and commercial fans please refer to AMCA Publication 410 Electrical Disconnects All fan motor...

Страница 4: ...ortant to reduce turbulence and damper flutter which may lead to premature damper failure Pre Installation Checks Fan Size Damper Size Square Recommended Wall Opening W O Square M Minimum Figure 1 Fig...

Страница 5: ...heavy motors and all Filtered Supply Wall Housings need additional bracing Typical Installation Check all fasteners and setscrews for tightness This is especially important for bearing setscrews The...

Страница 6: ...o the bearings In addition check all fasteners attaching the motor to the motor plate Lubrication Many fractional horsepower motors installed on the smaller fans are lubricated for life and require no...

Страница 7: ...ises sometimes heard during operation by adjusting a simple setting on the controller Debris Remove all debris from the fan Fan does not operate Electrical supply Check fuses circuit breakers Check fo...

Страница 8: ...Phase _______ Actual Voltage ________ Hertz _______ Phase __________ Amps ________________ Mark _________________ Actual Amperage ______________________________________ Supply hp ____________ Exhaust...

Отзывы: