(6) Before performing the air-tightness test to the refrigerant pipes, do not conduct insulation or
wrapping at the welding or flaring opening joints of the IDU. The pressure must be increased
simultaneously for pipes on outdoor sides and cannot be increased for pipes on one side.
Before performing the air-tightness test, do not conduct insulation or wrapping at the welding joints,
Otherwise, leak source cannot be detected quickly.
2 VACUUMIZATION AND DESICCATION FOR THE SYSTEM
2.1 Requirements on the Vacuum Pump
The vacuum pump for different refrigerant systems cannot be the same.
The ultimate vacuum degree of the vacuum pump should reach -0.1 MPa.
The air discharge capacity of the vacuum pump must be greater than 4 L/S.
The precision of the vacuum pump must be greater than 0.02 mmHg.
The system vacuum pump must be equipped with a check valve.
2.2 Procedure and Precautions for Vacuumization and Desiccation
2.2.1 Procedure
(1) Before vacuumization, ensure that the stop valves of the gas and liquid pipes are turned off.
(2) Use the perfusing duct to connect the regulator valve and vacuum pump to detection
connectors of the gas pipe and liquid pipe.
(3) Vacuumize for 4 hours and check whether the vacuum degree reaches -0.1 MPa or more. If
not, leakage may exist. Perform leakage check again. If no leakage exists, continue to vacuumize for 2
hours.
(4) If the vacuum degree cannot be kept after vacuumization is performed for twice, there may be
water in the pipe when it is confirmed that no leakage exists. In this case, discharge water by means of
vacuum breaking. Perfuse nitrogen at 0.05 MPa to the pipe. Vacuumize for 2 hours and keep vacuuming
Содержание Ultra Heat GMV-VQ72W/A-F
Страница 1: ...Ultra Heat GMV Multi VRF TECHNICAL SERVICE MANUAL R410A Heat Recovery Series ...
Страница 26: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 22 CHAPTER 2 INSTALLATION ...
Страница 30: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 26 ...
Страница 73: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial INSTALLATION 69 ...
Страница 120: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 116 CHAPTER 4 MAINTENANCE ...
Страница 135: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 131 ...
Страница 136: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 132 2 System high pressure protection E1 ...
Страница 137: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 133 3 System low pressure protection E3 ...
Страница 167: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 163 PFC board Drive board ...
Страница 203: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 199 5 4 NCHS4B U ...
Страница 205: ...Ultra Heat GMV VRF Technical Service Manual_Heat Recovery Serial MAINTENANCE 201 5 5 NCHS8B U ...
Страница 207: ...Jf00303410 ...