Gree RIO09HP115V1A - отличный выбор для кондиционирования воздуха. Установите его с помощью подробной инструкции в установочном руководстве. Скачайте его бесплатно на manualshive.com. Получите руководство пользователя и наслаждайтесь прохладой!
Models:
CROWN09HP230V1A
CROWN12HP230V1A
CROWN18HP230V1A
HIGH-WALL DUCTLESS AIR CONDITIONING & HEATING SYSTEM INSTALLATION MANUAL
Страница 1: ...Models CROWN09HP230V1A CROWN12HP230V1A CROWN18HP230V1A HIGH WALL DUCTLESS AIR CONDITIONING HEATING SYSTEM INSTALLATION MANUAL ...
Страница 2: ...er and Wiring Installation 17 19 Testing and Inspection 20 23 Troubleshooting 24 25 Diagnostic Codes 26 28 Care and Cleaning 29 Thank you for choosing a Crown High Wall Unit for your customer Please read this installation manual carefully before installing and starting up the Crown System Take a moment to fill out the product and installation form on the back cover Retain both the manual and insta...
Страница 3: ...practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation This appliance is not intended for use by children without responsible adult supervision Proper care should be taken to ensure safety Heat pumps air conditioners heating equipment should be installed started up ...
Страница 4: ...ock out and tag all switches with a warning label General Safety Precautions A dedicated power supply circuit should be used in accordance with local electrical safety regulations and National Electrical Codes NEC Ensure that the entire system is properly grounded Use a properly sized circuit breaker to protect equipment against short circuit and overload conditions The system must be positioned a...
Страница 5: ...ries Designation Revision Level Style Color Designation Example CROWN12HP230V1AO O 12 HP 230V 1 A TERRA RIO NEO CROWN Model Type AC Cooling Only HP Heat Pump Product Type S System O Outdoor units H Indoor High Wall Electrical Rating 230V 208 230V 60Hz 1PH NOMENCLATURE 4 ...
Страница 6: ... OD 7 16 in ID Unit Size BtuH Liquid Line Suction Gas Line 9 000 1 4 6 1 2 12 12 000 1 4 6 1 2 12 18 000 1 4 6 5 8 15 Unit Size BtuH Min Line Length Max Line Length Max Elevation 9 000 10 3 25 7 5 49 15 33 10 12 000 10 3 25 7 5 66 20 33 10 18 000 10 3 25 7 5 82 25 33 10 Unit Size BtuH Refrigerant Type Factory System Charge Additional Charge oz kg oz ft g m 9 000 R410A 49 4 1 4 0 2 20 12 000 R410A ...
Страница 7: ...rench Hex Keys orAllenWrenches Drill Drill Bits Hole Saw Pipe Cutter Screw drivers Phillips Flat blade Manifold and Gauges Level R410A FlaringTool Clamp onAmp Meter Vacuum Pump Safety Glasses Work Gloves Refrigerant Scale Micron Gauge SUGGESTEDTOOLS 6 ...
Страница 8: ...PART NAMES Indoor unit Part Name 1 Front Panel 2 Filter 3 Remote Controller 4 Inter Connection Wire 5 Drain Hose 6 Refrigerant Lines Outdoor unit 3 Air outlet Air inlet Air inlet Air outlet 2 1 4 5 6 7 ...
Страница 9: ...be easily made to outdoor unit 5 Indoor unit is out of reach of children 6 A mounting wall strong enough to withstand four times the full weight and vibration of the unit 7 Filter can be easily accessed for cleaning 8 Leave enough free space to allow access for routine maintenance 9 Install at least 10 ft 3 m away from the antenna ofTV set or radio Operation of the air conditioner may interfere wi...
Страница 10: ...nsure proper airflow 5 Wall or roof is strong enough to withstand the full weight and vibration of the outdoor unit for wall or roof installation only 6 Outdoor unit is out of reach of children and does not obstruct walkways 7 Outdoor unit is not exposed to direct sunlight excessive dust or strong wind 8 Condensate water can drain freely during heating 9 Maintenance and repairs can be easily perfo...
Страница 11: ...tering mark on mounting bracket for centering the indoor unit on the wall 5 Mounting bracket must be installed horizontally and level right to left NOTE Condensate drain pan has built in pitch for proper drainage 6 Secure mounting bracket to wall with a minimum of five screws evenly spaced to properly support indoor unit weight NOTE It is recommended to install screw anchors for sheet rock concret...
Страница 12: ...30V1AO 21 7 14 9 23 5 35 4 13 9 551 378 597 899 353 CROWN18HP230V1AO 24 0 16 8 31 1 38 6 15 6 610 427 790 980 396 OUTDOOR UNIT DIMENSIONS in mm Model A B C CROWN09HP230V1AO 37 8 12 6 8 0 960 320 205 CROWN12HP230V1AO 37 8 12 6 8 0 960 320 205 CROWN18HP230V1AO 37 8 12 6 8 0 960 320 205 INDOOR UNIT DIMENSIONS in mm B D C E A B C A ...
Страница 13: ... drainage NOTE To meet FloridaWind Load criteria the outdoor unit must be anchored to concrete pad using four 3 8 in diameter PowerWedge Bolt Plus or equivalent with 1 in diameter fender washers Anchor bolts must be embedded into 3 000 PSI minimum concrete at a distance of 41 2 in from any concrete edge The concrete thickness must exceed 1 5 times the anchor depth Condensate Drain Installation for...
Страница 14: ...nate outdoor air and water leaks into the living space PIPING INSTALLATION Refrigerant Piping NOTE Expandable foam insulation may be added to fill large wall gaps Apply per manufacturer s instructions Seal Hole Hole Size Indoor Outdoor Wall Hole Sleeve Wall Hole Diagram Drill Hole inWall If indoor unit refrigerant piping is going to exit from the rear 1 It is recommended that the refrigerant pipe ...
Страница 15: ...o the indoor unit 2 Adjust the length and carefully bend refrigerant pipes to meet indoor unit refrigerant pipe connections with proper tools to avoid kinks 3 Apply a small amount of refrigerant oil to the flare connection on the refrigerant pipes Piping Preparation 1 Do not open service valves or remove protective caps on pipes until all connections are made 2 Keep tubing free of dirt sand moistu...
Страница 16: ... re flare refrigerant pipes if required An R410A FlaringTool is required for re flaring refrigerant pipes 3 Apply a small amount of refrigerant oil to the flare connection on the refrigerant pipe 4 Properly align piping and tighten flare nut using a standard wrench and a torque wrench as shown in the indoor piping section 5 Carefully tighten flare nuts to correct torque level referring to theTorqu...
Страница 17: ...be required 2 Apply pipe insulation to the entire drain line and joints to prevent sweating 3 The through wall hole for the drain hose must be lower than the indoor wall unit drain outlet for a functional gravity drain system 4 Install field supplied drain hose with a downward slope from the Indoor wall unit drain outlet to the drain hose outlet 5 Route the condensate drain hose in the safety loca...
Страница 18: ... 3 GND L1 2 L2 GND GND L2 L1 Black Brown Grn Yel Interconnecting Wires Main Power Wires Outdoor Unit Indoor Unit Black White Grn Yel Blue Black Brown Grn Yel Outdoor Unit Indoor Unit N 1 2 3 GND N 1 2 3 L1 L2 GND Interconnecting Wires 18 000 BtuH Black White Grn Yel Main Power Wires GND L2 L1 17 ...
Страница 19: ...nit wire connections 3 Connect wiring to indoor unit per system wiring diagram NOTE The indoor unit is powered from the outdoor unit depending on local code a disconnect switch may need to be installed to a power supply circuit 4 Replace field wiring cover and close front cover of indoor unit Indoor Disconnect Switch If required Local codes may require a disconnect switch within sight of the indoo...
Страница 20: ...n and possible damage 6 Tightly connect main power wires to outdoor unit terminal block per system wiring diagram 7 Secure all wires inside wire clamp strain relief Verify wires are secure not loose and no external force on wires affects the connections at the terminals 8 Replace service panel on right side of the outdoor unit 9 Connect main power wires and conduit to unit disconnect switch box fi...
Страница 21: ...inutes for the 9 000 BtuH units to 1 hour for a larger 36 000 BtuH unit 6 Close the manifold valves and shut off the pump a If vacuum holds below 700 microns for 15 minutes the system can be considered dry and leak free Go to step 5 b If vacuum increases to 800 microns or greater this is an indication of moisture in system or a leak exist Identify leak and repair as necessary after which repeat st...
Страница 22: ...0 0 2 oz ft 18 000 0 5 oz ft Vacuum Procedure con t 7 Confirm that manifold valves are closed and disconnect the vacuum pump 8 Open the service valves to the fully back seat position to let the refrigerant flow to the indoor unit and balance the pressure in system Important Do not allow air to enter the connection pipe when removing the hose 9 Replace service valve caps and tighten Oil return bend...
Страница 23: ...Put batteries in the remote controller and hold it 5 or 6 feet from the Crown indoor wall unit 3 Point the remote controller at the Crown indoor wall unit and press the Sync button for 3 seconds 4 The Crown indoor wall unit will provide 3 beeps to signal a successful match 5 Press the Power ON button on the remote controller The green indicator light will display on the Crown indoor wall unit 6 Th...
Страница 24: ...ting Verify the indoor discharge air is cooling the room Press the Mode button to Heating Adjust the room setpoint to bring the system on in heating mode The system should start heating mode within 3 5 minutes Verify the outdoor fan and compressor are operating Verify the indoor fan is operating Verify the indoor discharge air is heating the room Press the OFF button on the remote controller Verif...
Страница 25: ...se It is normal for the system to emit a slight fog or water vapor when cooling extremely humid warm air Solution The fog or water vapor will disappear as the system cools and dehumidifies the room space Cause It is normal for the system to make slight cracking sounds from parts expanding and contracting during system starts and stops Solution The noises will discontinue as temperature equalizes a...
Страница 26: ...eries might be low Change the batteries The remote controller must be within 25 ft 7 5 m with no obstructions of the indoor unit If remote controller needs to be replaced contact a qualified service professional for assistance In the meantime use the Aux button to operate the system Cause There are a number of system functions that will prevent air flow Solution Check for the following In heating ...
Страница 27: ...ystem load is too high 3 Indoor coil is blocked or dirty 1 Communication cable is mis wired between indoor and outdoor units 2 Indoor or Outdoor control board malfunction 1 Incorrect refrigerant charge level 2 Refrigerant metering device malfunction 3 Compressor malfunction Control board malfunction 1 No jumper cap inserted on the control board 2 Incorrect or damaged jumper cap on control board 3 ...
Страница 28: ...perature sensor damaged 3 Control board malfunction 1 Loose or bad connection between sensor and control board 2 Outdoor coil temperature sensor damaged 3 Control board malfunction 1 Loose or bad connection between sensor and control board 2 Discharge temperature sensor damaged 3 Control board malfunction 1 Supply voltage on L1 and N is above 265Vac 2 Capacitor on control board malfunction 3 Outdo...
Страница 29: ...malfunction 3 Compressor malfunction 1 Mis wiring of the reactor filter and PFC capacitor 2 Reactor filter or PFC capacitor malfunction 3 Control board malfunction 1 Loose connections between fan motor and control board 2 Fan motor malfunction 3 Control board malfunction Indoor and outdoor units are not compatible 1 Over charged with refrigerant 2 Control board malfunction 3 Compressor malefaction...
Страница 30: ...rs will affect the performance and the longevity of your unit It is recommended that air filters be cleaned every three 3 months To access and clean the filter CARE AND CLEANING 1 Open Front Panel Firmly grasp both sides of the front panel and pull upward to about 60 degree angle NOTE do not force panel open 2 Remove Filter Remove the filter as indicated in the figure at right 3 Clean Filter Use v...
Страница 31: ...mation along with the installation data and dealer contact information will be helpful should your system require maintenance or service UNIT INFORMATION Outdoor Unit Model No Serial No Indoor Unit Model No Serial No INSTALLATION INFORMATION Date Installed DEALERSHIP INSTALLER INFORMATION Company Name Address Phone Number Technician Name Gree Electric Appliances Inc 2015 Cat No DFS CROWN HP 1IN ...