Installation and Maintenance
Service Manual
Appendix:
1.Standard length of connection pipe(More details please refer to the specifications.)
2.Min length of connection pipe for the unit with standard connection pipe of 5m, there is no limitation for themin length of connection pipe.
For the unit with standard connection pipe of 7.5m and 8m, the min length of connection pipe is 3m.
3.Max. length of connection pipe and max. high difference.(More details please refer to the specifications.)
4.The additional refrigerant oil and refrigerant charging required after prolonging connection pipe
● After the length of connection pipe is prolonged for 10m at the basis of standard length, you should add 5ml of refrigerant oil for each
additional 5m of connection pipe.
● The calculation method of additional refrigerant charging amount (on the basis of liquid pipe):
● Basing on the length of standard pipe, add refrigerant according to the requirement as shown in the table. The additional refrigerant
charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Appendix 2: Configuration of Connection Pipe
Set temperature
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Ambient temperature
Fahrenheit display
temperature
(
℉
)
Fahrenheit
(
℉
)
Celsius
(
℃
)
Fahrenheit display
temperature
(
℉
)
Fahrenheit
(
℉
)
Celsius
(
℃
)
Fahrenheit display
temperature
(
℉
)
Fahrenheit
(
℉
)
Celsius
(
℃
)
32/33
32
0
55/56
55.4
13
79/80
78.8
26
34/35
33.8
1
57/58
57.2
14
81
80.6
27
36
35.6
2
59/60
59
15
82/83
82.4
28
37/38
37.4
3
61/62
60.8
16
84/85
84.2
29
39/40
39.2
4
63
62.6
17
86/87
86
30
41/42
41
5
64/65
64.4
18
88/89
87.8
31
43/44
42.8
6
66/67
66.2
19
90
89.6
32
45
44.6
7
68/69
68
20
91/92
91.4
33
46/47
46.4
8
70/71
69.8
21
93/94
93.2
34
48/49
48.2
9
72
71.6
22
95/96
95
35
50/51
50
10
73/74
73.4
23
97/98
96.8
36
52/53
51.8
11
75/76
75.2
24
99
98.6
37
54
53.6
12
77/78
77
25
Fahrenheit display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
Fahrenheit display
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
61
60.8
16
69/70
69.8
21
78/79
78.8
26
62/63
62.6
17
71/72
71.6
22
80/81
80.6
27
64/65
64.4
18
73/74
73.4
23
82/83
82.4
28
66/67
66.2
19
75/76
75.2
24
84/85
84.2
29
68
68
20
77
77
25
86
86
30
Additional refrigerant charging amount for R22, R407C, R410A and R134a
Diameter of connection pipe
Outdoor unit throttle
Liquid pipe
Gas pipe
Cooling only(g/m)
Cooling and heating(g/m)
1/4”
3/8” or 1/2”
15
20
1/4” or 3/8”
5/8” or 3/4”
15
50
1/2”
3/4” or 7/8”
30
120
5/8”
1" or 1 1/4”
60
120
Содержание N00600
Страница 1: ...Service Manual Change for life GREE ELECTRIC APPLIANCES INC OF ZHUHAI 4LIV09 24 Models ...
Страница 93: ...90 Installation and Maintenance Service Manual INTENTIONALLY BLANK ...
Страница 95: ...92 Installation and Maintenance Service Manual INTENTIONALLY BLANK ...
Страница 96: ...93 Installation and Maintenance Service Manual INTENTIONALLY BLANK ...