6 Electric Control Cabinet
6.1 Wiring for Output Control Lines
Note:
The output control lines of the auxiliary electric heater 1, auxiliary electric heater 2 and the water pump
AC contactor are allowed to the terminal boards 11/12/13/14/15/16 of any module.
6.2 Specification of Power Cord and Air Switch
Model
Power Supply
Min. sectional area of
the power cable (mm
2
)
Capability of
the Air Switch
(A)
Live Line
Neutral Line
Earth Line
LSQWRF65M/D-M
LSQWRF65M/NaD-M
380-415V 3N 50Hz
16
16
16
63
LSQWRF80M/D-M
LSQWRF80M/NaD-M
25
16
16
80
LSQWRF130M/D-M
LSQWRF130M/NaD-M
50
25
25
125
LSQWRF160M/D-M
LSQWRF160M/NaD-M
70
35
35
160
Notes:
(a)
The specifications of the breaker and power cable listed in the table above are determined based on
the maximum power (maximum amps) of the unit.
(b)
The specifications of the power cable listed in the table above are applied to the conduit-guarded multi-
wire copper cable (like, JYV copper cable, consisting of PV insulated wires and a PVC cable jacket)
used at 40
℃
and resistible to 90
℃
(see IEC60364-5-523:1999). If the working condition changes, they
should be modified according to the related national standard.
(c)
The specifications of the breaker listed in the table above are applied to the breaker with the working
temperature at 40
℃
. If the working condition changes, they should be modified according to the related
national standard.