Multi Variable Air Conditioners Fresh Air Series Indoor Unit
12
4.2 Pipe Connection
(1) Direct the flaring of copper pipe to the center of screwed connection and then screw the flaring
nut tight as shown in Fig.4.2.
(2) Use a torque wrench to tighten up the flaring nut until the wrench gives out a click sound.
Fig.4.2
Torque for tightening nut
Pipe diameter (mm)
Torque (N·m)
Φ6.35
15~30
Φ9.52
35~40
Φ12.7
45~50
Φ15.9
60~65
Φ
19.05
70~75
(3) The pipe should not be bent too much or it may crack. Use a pipe bender when bending the
pipe.
(4) Use a sponge to wrap the uninsulated connection pipe and the joint. Then tie it tight with a
plastic tape.
4.3 Installation and Test of Drain Pipe
4.3.1 Notice for Installation of Drain Pipe
(1) It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines which
are likely to produce corrosive or peculiar smell to prevent the smell from entering indoors or
corrupt the unit.
(2) It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water from
pouring in and cause property loss or personal injury.
(3) Condensate drain pipe should be connected into special drain system for air conditioner.
(4) The drain pipe should be as short as possible and slope downward for at least 1%~2% so that
condensate can drain out easily.
(5) Size of the drainage hose must not be smaller than that of the drain pipe.
(6) Install the drain pipe according to the following diagram and make it insulated. Improper
installation will lead to water leakage and furniture and other objects may get wet.
(7) You can buy local hard PVC pipe as drain pipe. When connecting the pipe, insert the end of
PVC pipe into the drain hole and then tighten it up with a drain hose and cable tie. Do not use
adhesives to connect drain hole and drain hose.
Содержание GMV-NX140P/A(X1.2)-K
Страница 28: ...Multi Variable Air Conditioners Fresh Air Series Indoor Unit 24 Fig 5 5...
Страница 31: ......