4.2 Refrigerant Pipe Connection 

(1)  Aim the flaring port of copper pipe at the center of screwed joint and then tighten the flaring nut 

with hand as shown in Fig.4.2. 

(2)  Tighten the flaring nut with torque wrench. 

 

Fig.4.2 

Pipe diameter(mm) 

Torque(N•m) 

6.35 

15~30 

9.52 

35~40 

12.7 

45~50 

15.9 

60~65 

(3)  Use pipe bend when bending the pipe and the bending angle should not be too small.   
(4)  Wrap the connection pipe and joint with sponge and then tie them firmly with tape. 

4.3 Drainage Pipe Installation and Drainage System Testing 

4.3.1 Notice for Installation of Drain Pipe 

(1)  It is not allowed to connect the condensate drain pipe into waste pipe or other pipelines which 

are likely to produce corrosive or peculiar smell to prevent the smell from entering indoors or 
corrupt the unit. 

(2)  It is not allowed to connect the condensate drain pipe into rain pipe to prevent rain water from 

pouring in and cause property loss or personal injury. 

(3)  Condensate drain pipe should be connected into special drain system for air conditioner. 
(4)  The drainage pipe should be short and the gradient downwards should be at least 1%~2% in 

order to drain condensation water smoothly. 

(5)  The diameter of drainage hose should be bigger or equal to the diameter of drainage pipe joint. 
(6)  Install drainage pipe according to the following Fig and arrange insulation to the drainage pipe. 

Improper installation may lead to water leakage and damp the furniture and other things in the 
room.   

(7)  You can buy normal hard PVC pipe used as the drainage pipe. During connection, insert the 

end of PVC pipe into the drainage hole and then tighten it with drainage hole and wire binder. 
Can’t connect the drainage hole and drainage hole with glue. 

(8)  When the drainage pipelines are used for several units, the position of pipeline should be about 

100mm lower than the drainage port of each unit. In this case, thicker pipes should be applied. 

Содержание GMV-ND22TD/A-T

Страница 1: ...Original Instructions Commercial Air Conditioners Multi Variable Air Conditioners One way Cassette Type Indoor Unit Models GMV ND22TD A T GMV ND28TD A T GMV ND36TD A T GMV ND45TD A T GMV ND50TD A T G...

Страница 2: ...used for long cut off the power supply please energize and preheat the unit in advance before reusing it 3 Please properly select the model according to actual using environment otherwise it may impac...

Страница 3: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Страница 4: ...allation and Drainage System Testing 10 4 4 Panel Installation 13 4 5 Wired Controller Installation 15 5 Wiring Work 15 5 1 Connection of Wire and Patch Board Terminal 16 5 2 Power Cord Connection 16...

Страница 5: ...ected to other units that have been confirmed as complying to corresponding partial unit requirements of this international standard The electrical interface shall comply with electrical security requ...

Страница 6: ...s or objects into air outlet or air return grille If you use gas heater or petroleum heater in the same room please open the door or window to maintain good air circulation in case the room may lack o...

Страница 7: ...disconnection device which has at least 3mm clearances in all poles and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules If the product needs to be installed...

Страница 8: ...r reference only please refer to the actual product the unit of dimension is mm 3 1 Standard Fittings Use the following provided accessories according to the requirement No Name Appearance Q ty Usage...

Страница 9: ...near air inlet and air outlet 5 Follow the installation distance required in the Fig below to ensure sufficient space for maintenance 6 The installation location should be far from heat sources flamm...

Страница 10: ...Total length of communication line between indoor unit and wired controller L m Wire size mm Material Standard Remarks Light Ordinary polyvinyl chloride sheathed cord 60227 IEC 52 60227 IEC 53 L 250 2...

Страница 11: ...sion of power cord and capacity of air switch Model Power Cord Size Air Switch Capacity A Minimum Sectional Area of Ground Wire mm Minimum Sectional Area of Power Cord mm GMV ND22TD A T GMV ND28TD A T...

Страница 12: ...erence cardboard on the installation position drill 4 holes according to the hole site on the cardboard as shown in Fig 4 1 2 diameter of drilling hole is according to the diameter of expansion bolt a...

Страница 13: ...n Refer to paper pattern of installation for ceiling opening dimension The center of ceiling opening is indicated on the paper pattern Fix the paper pattern to the unit with 4 screws and fix the corne...

Страница 14: ...e condensate drain pipe into rain pipe to prevent rain water from pouring in and cause property loss or personal injury 3 Condensate drain pipe should be connected into special drain system for air co...

Страница 15: ...applied 4 Insert the drainage hose into drain socket tighten the metal clamp securely 5 Warp the sealing pad over drain hose and metal clamp for heat insulation 6 Make sure to perform insulation work...

Страница 16: ...stall hanger bracket at intervals of 1000 1500mm Unit mm Fig 4 3 4 4 3 3 Test of Drainage System 1 Please test drainage system after electric work is finished Inject approximately 1L purified water to...

Страница 17: ...ump will stop automatically after running for 10min 2 During the test please carefully check the drainage joint make sure no any leakage occur 3 It s strongly recommended to do the drain test before c...

Страница 18: ...4 2 Panel Installation 1 Remove the grille from the panel and then open the horizontal louver 2 Aim the screw hole on panel at the corresponding screw hole on main unit 3 Screw up the screws on corres...

Страница 19: ...ns in order to ensure the units reliable running 6 Install circuit breaker for branch circuit according to related regulations and electrical standards 7 All wiring must use pressure terminal or singl...

Страница 20: ...the terminal 2 The connection of stranded wire as shown in Fig 5 1 2 1 Strip about 10mm insulation of the end of stranded wire by stripping and cutting tool 2 Loosen the wiring screws on terminal boa...

Страница 21: ...t the power cord to terminal L N 4 Fix the power cord with wiring clamp 5 3 Connection of Communication Wire between Indoor Unit and Outdoor Unit or Indoor Unit 1 Detach the electric box lid 2 Let the...

Страница 22: ...for Wired Controller 1 Detach the electric box lid 2 Let the communication wire pass through the wiring through holes 3 Connect the communication wire to terminal H1 and H2 of indoor 4 bit wiring boa...

Страница 23: ...that must be set as master one and slave one 4 One wired controller can control 16 indoor units in maximum at the same time As shown in Fig 5 5 NOTES The type of indoor units must be the same if they...

Страница 24: ...Multi Variable Air Conditioners One way Cassette Type Indoor Unit 20 Fig 5 5...

Страница 25: ...of Filter 1 Remove the filters from inlet of IDU Use a vacuum cleaner to remove dust If the filters are dirty wash them with warm water and mild detergent and dry the filters in the shade 2 If the un...

Страница 26: ...epair may cause electric shock or fire so please contact an authorized service center for professional service The following checks prior to contact may save your time and money Phenomenon Troubleshoo...

Страница 27: ......

Отзывы: