Multi Variable Air Conditioners One-way Cassette Type Indoor Unit
7
Material Type
Total Length L (m) of
Communication Cable
between Indoor Unit
and Indoor (Outdoor)
Unit
Wire size (mm
²
)
Material
Standard
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L≤1000
≥
2×0.75
IEC 60227-5
1. If the wire diameter is enlarged to
2×1mm², the total communication line
length can reach 1500m.
2. The cord shall be Circular cord (the
cores shall be twisted together).
3. If unit is installed in places with intense
magnetic field or strong interference, it is
necessary to use shielded wire.
3.4 Wiring Requirement
Dimension of power cord and capacity of air switch.
Model
Power Cord Size
Air Switch Capacity
(A)
Minimum Sectional
Area of Ground Wire
(mm
²
)
Minimum Sectional
Area of Power Cord
(mm
²
)
GMV-ND22TD/A-T
GMV-ND28TD/A-T
GMV-ND36TD/A-T
GMV-ND45TD/A-T
GMV-ND50TD/A-T
GMV-ND56TD/A-T
208-230V ~ 60Hz
220-240V ~ 50Hz
6
1.0
1.0
NOTES!
①
An all-pole disconnection switch having a contact separation of at least 3mm in all poles should
be connected in fixed wiring.
②
The circuit breaker and power cord specification in above sheet is based on max power (max
current) of the unit.
③
The power cord specification in above sheet is based on ambient temperature of 40
℃
.
④
The circuit breaker specification in above sheet is based on ambient temperature of 40
℃
. If the
working condition is different, please adjust it according to the specification sheet of circuit