Two-way Cassette Indoor Unit Owner's Manual
18
⑩
The communication wires should be separated from power cord and connection wire
between indoor unit and outdoor unit.
⑪
If the project needs higher static pressure, you can set it through the wired controller.
⑫
The appliance must be fitted with means for disconnection from the supply mains having a
contact separation in all poles that provide full disconnection under overvoltage category
III conditions, and these means must be incorporated in the fixed wiring in accordance
with the wiring rules.
5.1 Connection of Wire and Patch Board Terminal
(1) Connection of single branch wire (as shown in Fig 5.1.1)
1) Use a stripper to strip away about 25mm of the insulation layer at the end of single
branch line so that the single-core wire can be exposed.
2) Remove the wiring screws on the terminal board.
3) Shape the tail of wire into ring by needle nose plier, and keep the gauge of ring in
accordance with screw.
4) Lead the screw across the circle of the single branch line and fix it on the wiring board.
(2) Connection of multi-twisted wire (as shown in Fig 5.1.2)
1) Use a wired stripper to strip away about 10mm of the insulation layer at the end of
multi-twisted wire.
2) Loosen the wiring screws on patch board..
3) Use a round terminal fastener or a plier to securely fasten the round terminal with each
core wire of the multi-core wire.
4) Confirm the position of each core wire on the round terminal and then use a
screwdriver to tighten the terminal screw.
Fig 5.1.1 Fig 5.1.2
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.