Multi Variable Air Conditioners Indoor Unit for North America
64
4.4.1 Master IDU Settings
The master IDU can be set through the wired controller or remote controller. The methods for setting
the master IDU through the remote controller are as follows:
Step 1: Set an IDU to air-supply status and set the temperature to 30°C.
Step 2: Continuously press ―—‖ and ―+‖ for three times within five seconds.
Step 3: Check whether the setting is successful. If it is, the LED panel of the IDU will display "UC" for
five seconds and "MASTER" on the wired controller will be on. Otherwise, repeat steps 1 and 2.
4.4.2 Parameter Query
Engineering application functions cover parameter query and parameter settings.
For parameter query, users can query user parameters and engineering parameters of the unit. The
parameter query method is as follows:
(1) On the professional remote controller of YV1L1, press and hold "
CLOCK
" for five seconds to
enter the parameter query status. The viewing text is displayed. The query code "C00" blinks in the
temperature area.
(2) Press "
" to switch the query code and select a unit parameter to be queried (see Table 2.5
for parameters that can be queried).
(3) If the timer area displays query sub-items, it indicates that there are level 2 query menus. Press
"
MODE
" to enter level 2 query menu selection. The content blinks in the timer area. Press "
" to
switch query sub-items and select a level 2 menu to be queried.
(4) Press "
TEMP
" to confirm query and return to step 2.
After entering the engineering application function, the system automatically quits the engineering
commissioning status if no valid operations are performed within 20 seconds. To directly quit the
engineering commissioning status, press "
CLOCK
".
Table 2.5 Query Parameters
Query Code
Query Content
Query Sub-item
Level 2 Query Content
C00
Invalid
C01
Project number query of the current IDU
C02
Capacity query of the current IDU
C03
Indoor unit quantity query in the CAN1 network
C04
Project number query of the master IDU
C05
Historical fault query ingress of the current
IDU
01
Fault 1
02
Fault 2
03
Fault 3
04
Fault 4
05
Fault 5
C06
Preferential operation query
C07
Temperature query for environment temperature sensor of the current IDU
C08
Prompt time query for air filter cleaning
C10
Static pressure setting query of ODU
01
Module 1
02
Module 2
03
Module 3
Содержание GMV-N07G/A3A-D(U)
Страница 1: ...Multi Variable Air Conditioners Indoor Unit for North America Service Manual R410A R410A 60Hz GC201609...
Страница 7: ...ulti Variable Air Conditioners Indoor Unit for North America 1 PRODUCT...
Страница 36: ...Multi Variable Air Conditioners Indoor Unit for North America 30 CONTROL...
Страница 37: ...Multi Variable Air Conditioners Indoor Unit for North America 31 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 75: ...Multi Variable Air Conditioners Indoor Unit for North America 69 INSTALLATION...
Страница 111: ...Multi Variable Air Conditioners Indoor Unit for North America 105 MAINTENANCE...
Страница 192: ...Multi Variable Air Conditioners Indoor Unit for North America 1 JF00302921...