7 Error Indication 

Inquiry method of error indication: combine division symbol and content symbol to check  the 

corresponding error. 

Indoor: 

Error 

Code 

Content 

Error 

Code 

Content 

L0 

Malfunction of IDU (uniform) 

d1 

Indoor PCB is poor 

L1 

Protection of indoor fan 

d2 

Malfunction of lower water temperature sensor 

of water tank 

L2 

Auxiliary heating protection 

d3 

Malfunction of ambient temperature sensor 

L3 

Water-full protection 

d4 

Malfunction of entry-tube temperature sensor 

L4 

Abnormal power supply for wired controller 

d5 

Malfunction of middle temperature sensor 

L5 

Freeze prevention protection 

d6 

Malfunction of exit-tube temperature sensor 

L6 

Mode shock 

d7 

Malfunction of humidity sensor 

L7 

No main IDU 

d8 

Malfunction of water temperature sensor 

L8 

Power supply is insufficient 

d9 

Malfunction of jumper cap 

L9 

For single control over multiple units, number of 

IDU is inconsistent 

dA 

Web address of IDU is abnormal 

LA 

For single control over multiple units, IDU series is 

inconsistent 

dH 

PCB of wired controller is abnormal 

LH 

Alarm due to bad air quality 

dC 

Abnormal setting for capacity button 

LC 

IDU is not matching with outdoor unit 

dL 

Malfunction of air outlet temperature sensor 

LL 

Malfunction of water flow switch 

dE 

Malfunction of indoor CO

2

 sensor 

LE 

Rotation speed of EC DC water pump is abnormal 

dF 

Malfunction of upper water temperature sensor 

of water tank 

LF 

Malfunction of shunt valve setting 

dJ 

Malfunction of backwater temperature sensor 

LJ 

Setting of functional DIP switch code is wrong 

dP 

Malfunction of inlet tube temperature sensor of 

generator 

LP 

Zero-crossing malfunction of PG motor 

dU 

Malfunction of drainage pipe temperature sensor 

of generator 

LU 

Indoor unit’s branch is not inconsistent for 

one-to-more unit of heat recovery system 

db 

Debugging status 

Lb 

Inconsistent IDU of group-controlled reheat and 

dehumidification system 

dd 

Malfunction of solar power temperature sensor 

y1 

Malfunction of inlet tube temperature sensor 2 

dn 

Malfunction of swing parts 

y2 

Malfunction of outlet tube temperature sensor 2 

dy 

Malfunction of water temperature sensor   

y7 

Malfunction of fresh air intake temperature sensor 

y8 

Main error of indoor air box sensor 

yA 

IFD malfunction 

 

 

Outdoor: 

Error 

Code 

Content 

Error 

Code 

Content 

F0 

Main board of ODU is poor 

E0 

Malfunction of ODU (uniform) 

F1 

Malfunction of high-pressure sensor 

E1 

High-pressure protection 

F3 

Malfunction of low-pressure sensor 

E2 

Discharge low-temperature protection 

F5 

Malfunction of discharge temperature sensor of 

compressor 1 

E3 

Low-pressure protection 

F6 

Malfunction of exit-tube temperature sensor 

E4 

High discharge temperature protection of 

compressor 

F7 

Malfunction of humidity sensor 

Ed 

Drive module low temperature protection 

F8 

Malfunction of water temperature sensor 

J0 

Protection for other modules 

F9 

Malfunction of jumper cap 

J1 

Over-current protection of compressor 1 

FA 

Web address of IDU is abnormal 

J2 

Over-current protection of compressor 2 

FC 

Current sensor of compressor 2 is abnormal   

J3 

Over-current protection of compressor 3 

FL 

Current sensor of compressor 3 is abnormal 

J4 

Over-current protection of compressor 4 

FE 

Current sensor of compressor 4 is abnormal 

J5 

Over-current protection of compressor 5 

FF 

Current sensor of compressor 5 is abnormal 

J6 

Over-current protection for compressor 6 

FJ 

Current sensor of compressor 6 is abnormal 

J7 

Gas-mixing protection of 4-way valve 

Содержание GMV-36WL/C-T

Страница 1: ...Owner s Manual Original Instructions Commercial Air Conditioners DC Inverter Multi VRF System Applicable Models GMV 60WL C T U GMV 48WL C T U GMV 36WL C T U...

Страница 2: ...All graphics in this manual is only for your reference For sales or production reasons these graphics are subject to change by manufacturer without prior notice 9 This appliance is not intended for u...

Страница 3: ...Hole 5 4 2 Connection Pipe 6 4 3 Installation of Connection Pipe 10 4 4 Disassembly of Compressor Feet 14 4 5 Vacuum Pumping Refrigerant Adding 15 4 6 Electric Wiring 17 5 Check Items after Installati...

Страница 4: ...ephone line 6 Be sure to use special accessories and parts for installation to prevent water leakage electric shock and fire hazard etc 7 If refrigerant leakage happens please ventilate the room immed...

Страница 5: ...tely and then contact Gree appointed service center If those abnormal circumstances still exit the unit may be damaged and it may lead to electric shock or fire hazard 27 Do not repair the unit by you...

Страница 6: ...s of DC Inverter Multi VRF System can be connected to various indoor units When any one of the indoor units receives operating command outdoor unit will start operation as per required capacity When a...

Страница 7: ...for heat exchange and maintenance so that unit can operate reliably with good ventilation 7 Make sure the location has space for heat exchange and maintenance so that unit can operate reliably with go...

Страница 8: ...r piping work requirements R410A Refrigerant System Outer diameter mm inch Wall thickness mm inch 6 35 1 4 0 8 1 32 9 52 3 8 0 8 1 32 12 7 1 2 0 8 1 32 15 9 5 8 1 0 1 25 19 05 3 4 1 0 1 25 4 Installat...

Страница 9: ...inch Model A B C D E GMV 36WL C T U GMV 48WL C T U 900 35 3 8 340 13 3 8 1345 53 572 22 1 2 378 15 GMV 60WL C T U 940 37 320 12 9 16 1430 56 1 4 632 24 7 8 350 14 7 8 4 2 Connection Pipe 4 2 1 Schemat...

Страница 10: ...and Height Difference of Connection Pipe Piping parameters of GMV 36WL C T U GMV 48WL C T U GMV 60WL C T U Allowable value Fitting pipe m feet Total length actual length of fitting pipe 300 984 L1 L2...

Страница 11: ...le Pipe dimension Gas pipe mm inch Liquid pipe mm inch GMV 36WL C T U 15 9 5 8 9 52 3 8 GMV 48WL C T U 15 9 5 8 9 52 3 8 GMV 60WL C T U 19 05 3 4 9 52 3 8 4 2 4 Selection of Indoor Branches Select ind...

Страница 12: ...otal capacity of downstream indoor units C Btu h Pipe mm inch Liquid pipe mm inch C 19000 12 7 1 2 6 35 1 4 19000 C 48500 15 9 5 8 9 52 3 8 48500 C 76400 19 05 3 4 9 52 3 8 4 2 6 Dimension of Pipe bet...

Страница 13: ...le is not allowed 3 When laying the pipe be careful not to distort it Radius of bending parts should be over 200mm 8inch Note that pipes cannot be repeatedly bent or stretched otherwise the material w...

Страница 14: ...of nut will get damaged if the flared nut is twisted forcibly 3 Use torque wrench to twist on the flared nut tightly until the wrench gives out a click sound Hold the handle of wrench and make it at r...

Страница 15: ...ht or rear side Fig 4 13 2 Pipe connection for GMV 60WL C T U As shown in Fig 4 14 and Fig 4 15 open the outermost soundproof cotton and place a fire barrier between compressor and straight pipe Use a...

Страница 16: ...d remove burrs as well See Fig 4 17 3 Y type branch must be installed vertically or horizontally Fig 4 17 Branch shall be isolated by insulating material that can bear 120 C 248 F or even higher tempe...

Страница 17: ...perature For heat pump unit liquid pipe should bear 70 C 158 F or above and gas pipe should bear 120 C 248 F or above For cooling only unit both liquid pipe and gas pipe should bear 70 C 158 F or abov...

Страница 18: ...ds to be charged with additional refrigerant 2 Confirm whether outdoor liquid and gas valves are closed 3 Use vacuum pump to withdraw the air inside indoor unit and connection pipe from the outdoor va...

Страница 19: ...Quantity of IDU 2 0 3 kg 10 58oz First confirm that there is no leakage from the system When compressor is not working charge additional R410A with specific amount to the unit through the filling ope...

Страница 20: ...function and thermal trip function so that system can be protected from short circuit and overload 6 Air conditioner belongs to class I electrical appliance so it must be securely grounded 7 The yell...

Страница 21: ...ot being supplied to the indoor unit and outdoor unit 2 Match the terminal block numbers and connection cord colors with those of the indoor unit side Erroneous wiring may cause burning of the electri...

Страница 22: ...condition changes please adjust the specification according to national standard 3 Specification of circuit breaker is based on the working condition where ambient temperature of circuit breaker is 40...

Страница 23: ...DC Inverter Multi VRF System 20 Fig 4 26 Fig 4 27...

Страница 24: ...placing the main board of outdoor unit it is necessary to perform test operation and debugging Otherwise unit won t be able to work 2 Test operation and debugging must be performed by professional tec...

Страница 25: ...mmunication wire of IDU is correctly connected After the check connect power and start debugging from progress 01 If the number is then correct press main board s SW3 button to confirm Then the displa...

Страница 26: ...ts 08_ Confirm preheated compressor 08 U0 Display circularly Preheat time for compressor is less than 8 hours Display will be as in the left until the preheat time reaches 8 hours Press main board s S...

Страница 27: ...in this process through the L VALVE 15_ Cooling debugging 15 AC Display circularly Debugging for cooling mode If no malfunction occurs for 50min when compressor is running then the system is certifie...

Страница 28: ...ient temp is 25 35 C 77 95 F in cool mode system s high pressure value will be within 44 53 C 111 127 F In heat mode if ambient temp is above 5 C 23 F system s high pressure value is within 40 52 C 10...

Страница 29: ...or EXV varies within 40 480PLS 15 Communication parameters Communication data Number of IDUs detected by software is the same with the actual number No communication error 16 Drainage system Indoor un...

Страница 30: ...locked and dirty Clean the filter If problem cannot be solved after checking the above items please contact Gree service center and describe the cases and models Following circumstances are not malfun...

Страница 31: ...rossing malfunction of PG motor dU Malfunction of drainage pipe temperature sensor of generator LU Indoor unit s branch is not inconsistent for one to more unit of heat recovery system db Debugging st...

Страница 32: ...of outlet tube temperature sensor of condenser PA Malfunction of drive storage chip of compressor bJ High pressure sensor and low pressure sensor are connected reversely PH High voltage protection of...

Страница 33: ...en main control and DC DC controller U6 Alarm because valve is abnormal C2 Communication malfunction between main control and inverter compressor driver U7 Power grid DRED0 response protection C3 Comm...

Страница 34: ...connection pipe of ODU An Child lock status Ay Shielding status 8 Maintenance and Care Regular check maintenance and care can extend unit s service life Please have specialized person in charge of the...

Страница 35: ...ix oxygen C2H2 or other dangerous gas into the refrigerant circuit Otherwise it may lead to danger Use nitrogen or refrigerant to conduct the tests 9 After sales Service If there s quality defect or o...

Страница 36: ......

Отзывы: