INSTALLATION
1 Engineering Installation Preparation and Notice
1.1 Installation notice
Personnel and property safety are highly concerned during the entire installation process.
Installation implementation must abide by relevant national safety regulations to ensure personnel and
property safety.
All personnel involved in the installation must attend safety education courses and pass
corresponding safety examinations before installation. Only qualified personnel can attend the
installation. Relevant personnel must be held responsible for any violation of the regulation.
1.2 Installation key points and importance
VRF air conditioning systems use refrigerant, instead of other agent, to directly evaporate to carry
out the system heat. High level of pipe cleanness and dryness is required in the system. Since various
pipes need to be prepared and laid out onsite, carelessness or maloperation during installation may
leave impurities, water, or dust inside refrigerant pipes. If the design fails to meet the requirement,
various problems may occur in the system or even lead to system breakdown.
Problems that usually occur during installation are as follows:
No.
Installation Problem
Possible Consequence
1
Dust or impurities enter into the
refrigeration system.
Pipes are more likely to be blocked; air conditioning performance is
reduced; compressor wear is increased or even hinder the normal
operation of the system and burn the compressor.
2
Nitrogen is not filled into the refrigerant
pipe or insufficient Nitrogen is filled
before welding.
Pipes are more likely to be blocked; air conditioning performance is
reduced; compressor wear is increased or even hinder the normal
operation of the system and burn the compressor.
3
The vacuum degree in the refrigerant
pipe is insufficient.
The refrigeration performance is reduced. The system fails to keep
normal operation due to frequent protection measures. When the
problem getting serious, compressor and other major components can
be damaged.
4
Water enters into the refrigeration
system.
Copper plating may appear on the compressor and reduce the
compressor efficiency with abnormal noise generated; failures may
occur in the system due to ice plug.
5
The refrigerant pipe specifications do not
meet the configuration requirements.
Smaller configuration specifications can increase the system pipe
resistance and affect the cooling performance; larger configuration
specifications are waste of materials and can also reduce the cooling
performance.
6
Refrigerant pipe is blocked.
The cooling performance is reduced; in certain cases, it may cause
long-term compressor operating under overheat conditions; the
lubricating effect can be affected and the compressor may be burnt if
impurities were mixed with the lubricating oil.
7
Refrigerant pipe exceeds the limit.
The loss in pipe is considerable and the unit energy efficiency
decreases, which are harmful for long-term running of the system.
8
Incorrect amount of refrigerant is filled.
The system cannot correctly control the flow allocation; the
compressor may be operating under over-heating environment or
running when the refrigerant flows back to the compressor.
Содержание GMV-24WL/C-T
Страница 1: ...DC Inverter Side Discharge VRF for North America Capacity 24 kBtu h 60 kBtu h Rated Frequency 60 Hz...
Страница 4: ...GREE DC Inverter Side Discharge VRF for North America 1 PRODUCT...
Страница 12: ...GREE DC Inverter Side Discharge VRF for North America 9 CONTROL...
Страница 17: ...GREE DC Inverter Side Discharge VRF for North America 14...
Страница 18: ...GREE DC Inverter Side Discharge VRF for North America 15 Button Graphics...
Страница 65: ...GREE DC Inverter Side Discharge VRF for North America 62 Switchover of Software Languages...
Страница 66: ...GREE DC Inverter Side Discharge VRF for North America 63 INSTALLATION...
Страница 98: ...GREE DC Inverter Side Discharge VRF for North America 95 MAINTENANCE...
Страница 115: ...GREE DC Inverter Side Discharge VRF for North America 112 GMV 36WL A T U GMV 48WL A T U GMV 36WL C T U GMV 48WL C T U...
Страница 116: ...GREE DC Inverter Side Discharge VRF for North America 113 GMV 60WL A T U 4 Removal of Parts GMV 60WL C T U...
Страница 150: ...JF00302320...