Gree GMV6 DC Inverter VRF Units Service Manual
317
Appendix 3 Pressure Sensor Voltage and Pressure Table
High-pressure sensor features (R410A)
Temperature
(°C)
Absolute pressure
(kPA)
Voltage (V)
Temperature
(°C)
Absolute pressure
(kPA)
Voltage (V)
-40
176
0.102
16
1300
1.3
-39
184
0.111
17
1337
1.34
-38
193
0.12
18
1375
1.38
-37
202
0.13
19
1413
1.421
-36
211
0.139
20
1453
1.463
-35
220
0.149
21
1493
1.506
-34
230
0.16
22
1535
1.551
-33
240
0.17
23
1577
1.596
-32
250
0.181
24
1620
1.641
-31
261
0.193
25
1664
1.688
-30
273
0.206
26
1708
1.735
-29
283
0.216
27
1754
1.784
-28
295
0.229
28
1801
1.834
-27
307
0.242
29
1848
1.884
-26
319
0.255
30
1897
1.937
-25
332
0.268
31
1946
1.989
-24
345
0.282
32
1996
2.042
-23
359
0.297
33
2048
2.098
-22
373
0.312
34
2100
2.153
-21
388
0.328
35
2153
2.21
-20
403
0.344
36
2208
2.268
-19
418
0.36
37
2263
2.327
-18
434
0.377
38
2320
2.388
-17
450
0.394
39
2377
2.448
-16
467
0.412
40
2436
2.511
-15
484
0.43
41
2495
2.574
-14
502
0.45
42
2556
2.639
-13
520
0.469
43
2618
2.705
-12
538
0.488
44
2681
2.772
-11
558
0.509
45
2745
2.841
-10
577
0.53
46
2810
2.91
-9
597
0.551
47
2876
2.98
-8
618
0.573
48
2944
3.053
-7
639
0.596
49
3013
3.126
-6
661
0.619
50
3083
3.201
-5
684
0.644
51
3154
3.277
-4
707
0.668
52
3226
3.353
-3
730
0.693
53
3300
3.432
-2
754
0.718
54
3374
3.511
-1
779
0.745
55
3450
3.592
0
804
0.772
56
3528
3.675
1
830
0.799
57
3606
3.759
Содержание GMV-1015WM/G-U
Страница 212: ...Gree GMV6 DC Inverter VRF Units Service Manual 210 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 229: ...Gree GMV6 DC Inverter VRF Units Service Manual 227 Models GMV 400WM G U GMV 450WM G U GMV 504WM G U...
Страница 234: ...Gree GMV6 DC Inverter VRF Units Service Manual 232...
Страница 264: ...Gree GMV6 DC Inverter VRF Units Service Manual 262...
Страница 325: ...Gree GMV6 DC Inverter VRF Units Service Manual 323 GMV 400WM G U GMV 450WM G U and GMV 504WM G U...
Страница 331: ...JF00304610...