Owner's Manual
Original Instructions
Intelligent Converter
Models:
GIE-ADC12K5E
Страница 1: ...Owner s Manual Original Instructions Intelligent Converter Intelligent Converter Models GIE ADC12K5E ...
Страница 2: ......
Страница 3: ...ht possibly result in personal harm to the user or damage to property NOTICE is used to address practices not related to personal injury 1 Please read this manual before operation 2 There is a risk of electric shock and make sure the unit can be earthed properly 3 After power outage wait for at least 5 minutes before proceeding any other work 4 Pay attention to the hot surface to avoid being scald...
Страница 4: ......
Страница 5: ...mpany After the application is approved the user may install an electric meter to enjoy national or local subsidies For details on local policies consult local grid company If the user does not follow the method the manufacturer specifies to use the converter the converter protection measure may fail The converter must be maintained or repaired by professional personnel In case of any damage conta...
Страница 6: ......
Страница 7: ...SPORT STORAGE AND INSTALLATION 3 7 WIRING 7 7 1 CONVERTER TERMINALS 9 7 2 CONVERTER OUTPUT DC BUS TERMINALS 10 7 3 CONVERTER PV INPUT CABLE CONNECTION 11 7 4 CONVERTER AC WIRING 13 8 REMOVER OPERATION METHOD 14 9 INSPECTION AND TEST OPERATION 14 10 PRODUCT MODELS AND TECHNICAL SPECIFICATIONS 15 11 PV SYSTEM INSTALLATION PROJECT 17 ...
Страница 8: ......
Страница 9: ...1 copy Printout Barcode 1 copy Printout Installation confirmation receipt 1 copy Printout Packing list 1 copy Screws M6X23 4 sets For installing mounting base 3 Operation Method Power on the converter 1 Ensure that the DC input AC output and communication terminal of the converter are connected as required 2 Turn on the AC and DC protection switches 3 After system self check the converter enters t...
Страница 10: ...ult mode this indicator is off FAULT Red fault indicator In non fault mode this indicator is off If the converter does not receive CAN data within 30 seconds it reports a communication fault and this indicator is steady on In case of a fault this indicator flashes according to the Morse code and display interval in the table below based on fault types Error code range 00 99 Note The following tabl...
Страница 11: ...s not put into use immediately store it following the requirements below 1 Put the machine and accessories back into the box seal the box with tape and put the box in a clean and dry place to avoid dust and vapor entering the box 2 Ensure that the storage place is free of hazardous gases flammables explosives and corrosives Keep the temperature in the range from 25 C to 60 C and relative humidity ...
Страница 12: ...ance 3 Do not install the converter on flammable wall or in space containing flammable gases and materials 4 Keep the converter vertically installed to facilitate heat dissipation Do not lay the converter horizontally tilt or upside down 5 The converter is rated IP54 and suitable for indoor and outdoor installation 6 The installation altitude should not exceed 2000 m with ambient temperature in th...
Страница 13: ...ll the converter in a sealed box otherwise the converter fails to work properly or is damaged 9 Exposure to sunlight rain or snow directly affects the service life of converter If such impacts are unavoidable properly cover the converter to ensure optimal running state Installation Upright If the converter installed on the flat roof 4 bulgy bolts are needed M8 60 The user can use other suitable bu...
Страница 14: ...60 4 20N m The DC and AC output circuits are isolated from the enclosure and that system grounding if required by Section 250 of the National Electrical Code ANSI NFPA 70 is the responsibility of the installer This unit is intended for operation in an environment having a maximum ambient temperature of 50 degrees C ...
Страница 15: ...ther external protectors CAUTION Configure two channel PV input for the converter The maximum current of each channel is 14A You are advised to select two 14A 1000VDC circuit breakers complying with UL standard requirements as external protectors That is each channel is allocated a protector Total circuit breaker capacity A Recommended conductive wire Sectional area mm 2 quantity 14 2 2 0 4 The cu...
Страница 16: ... operation or failure to operate the converter as instructed may cause danger to users and result in major hardware damage even property loss or personal injury Please read this manual carefully before operation and observe the following safety instructions strictly Before operation disconnect the converter from a grid and avoid touching any terminal or conductor connected with the grid and PV inp...
Страница 17: ...ected according to positive and negative polarities voltage 1000V DC VDC power output port VDC and VDC VDC power output port connected according to positive and negative polarities voltage DC400V 780V AC power port AC AC port three phase AC power input and output identified L1 L2 and L3 Power supplies support 208V 240V which can be selected by configuration COM ports RS485 Implements data exchange...
Страница 18: ...485 CAN ETH 430009060002 Socket RCP 5SPFFH SCM70 01 Waterproof RJ45 430009060005 Socket RCP 00BMMS SL M7001 Waterproof RJ45 wire end USB 430009060004 USB socket SPAUA 20PMFP CA P 430009060004 USB socket cover SPAUA 20PMFP CAP 7 2 Converter Output DC Bus Terminals Terminal Type Converter Terminal Socket Match Optional Wire Terminal Plug Silkscreen Name Code Model Code Name DC VDC 44040024 Mould cas...
Страница 19: ...ector 2 1971914 1 3 RS485 CK 8C8P connector 4 CK 8C8P connector 3 CK 8C8P connector 2 CK 8C8P connector 1 UL2464 AWG26 X3 CK 8C8P connector 4 CK 8C8P connector 3 CK 8C8P connector 2 CK 8C8P connector 1 Note The RS485 cables connected with the DC electric devices are optional Communication wire assembly method 1 Turn the protective cover counterclockwise to remove it 2 If the COM port is unused ins...
Страница 20: ...onverter bottom namely the PV1 and PV1 DC connector PV2 and PV2 DC connector Specific operation is shown in the following figure Insert a remover into the hole to pull a connector downward Hole Plug Remover 2 Loosen the nut on the DC connector and take out the plug 3 Peel 10 mm insulation layer from the DC cable 4 Use a crimp to press the exposed cable core about 10 mm to the DC terminal as shown ...
Страница 21: ...ltage short circuit current installation angle and direction 1 Connect multiple PV panels in serial mode and ensure the sum of the open circuit voltage of the panels under proper light conditions does not exceed 1000VDC 2 Connect the PV panels to the converter accordingly connect positive to PV1 PV2 and negative to PV1 PV2 7 4 Converter AC Wiring Converter and Grid Connection Method Rated current ...
Страница 22: ...to remove the connector If a DC connector needs disassembly use a remover as shown in to tighten or loosen a nut Hole Remover Nut Keep the remover safe for use in future 9 Inspection and Test Operation Before test operation check the following items 1 Converter position facilitates operation and maintenance 2 The converter is firmly installed ...
Страница 23: ... array so that it starts to supply power When the converter changes to running state it works properly 10 Product Models and Technical Specifications G IEMS Intelligent Converter GIE ADC12K5E Max PV Input Voltage OC 1000VDC Isc PV 39A Max continuous input current 2 14A Max PV Input Power 14kW MPPT Range 400V 780V Max DC continuous output current 25A Rated DC output Current 25A DC output Voltage 40...
Страница 24: ... C Operating Temperature range 20 to 50 INTERCONNECTION INTEGRITY TEST CATEGORIES C62 42 2 Ring Wave Surge Category B C62 42 2 Combination Wave Surge Category B C37 90 1 RF Immunity compliance Yes C37 90 2 Communication circuit compliance Yes Utility interconnection voltage trip limits and trip times 208 V 240 V Magnitude Max Time Magnitude Max Time Overvoltage Fast 120 249 6V 0 16 Sec 288 0V 0 16...
Страница 25: ...ts cannot be used until they are accepted by the responsible department of the buyer During transport load and unload the converter with caution to avoid collision The PV components are placed on the joists Pressure must be proper enough so that the PV components and brackets can resist against wind and vibration and that glass is kept undamaged The PV components must be laid neatly with the wirin...