GREE GMV5 HR HEAT RECOVERY UNITS
152
CHAPTER 4 MAINTENANCE
PART 1 FAILURE CODE TABLE
1 System Failure Code Table
Indoor:
Error Code
Content
Error Code
Content
L0
Malfunction of IDU
d2
Malfunction of lower water temperature
sensor of water tank
L1
Protection of indoor fan
d3
Malfunction of ambient temperature sensor
L2
Auxiliary heating protection
d4
Malfunction of entry-tube temperature
sensor
L3
Water-full protection
d6
Malfunction of exit-tube temperature
sensor
L4
Abnormal power supply for wired controller
d7
Malfunction of humidity sensor
L5
Freeze prevention protection
d8
Malfunction of water temperature sensor
L7
No main IDU
d9
Malfunction of jumper cap
L8
Power supply is insufficient
dA
Web address of IDU is abnormal
L9
For single control over multiple units,
number of IDU is inconsistent
dH
PCB of wired controller is abnormal
LA
For single control over multiple units, IDU
series is inconsistent
dC
Setting capacity of DIP switch code is
abnormal
LH
Alarm due to bad air quality
dL
Malfunction of air outlet temperature
sensor
LC
IDU is not matching with outdoor unit
dE
Malfunction of indoor CO
2
sensor
LL
Malfunction of water flow switch
dF
Malfunction of upper water temperature
sensor of water tank
LE
Rotation speed of EC DC water pump is
abnormal
dJ
Malfunction of backwater temperature
sensor
LF
Malfunction of shunt valve setting
dP
Malfunction of inlet tube temperature
sensor of generator
LJ
Setting of functional DIP switch code is
wrong
dU
Malfunction of drainage pipe temperature
sensor of generator
LP
Zero-crossing malfunction of PG motor
db
Debugging status
LU
Indoor unit’s branch is not inconsistent for
one-to-more unit of heat recovery system
dd
Malfunction of solar power temperature
sensor
d1
Indoor PCB is poor
dn
Malfunction of swing parts
Outdoor:
Error Code
Content
Error Code
Content
E0
Malfunction of ODU
FH
Current sensor of compressor 1 is
abnormal
E1
High-pressure protection
FC
Current sensor of compressor 2 is
abnormal
E2
Discharge low-temperature protection
FL
Current sensor of compressor 3 is
abnormal
E3
Low-pressure protection
FE
Current sensor of compressor 4 is
abnormal
E4
High discharge temperature protection of
compressor
FF
Current sensor of compressor 5 is
abnormal
J0
Protection for other modules
FJ
Current sensor of compressor 6 is
abnormal
J1
Over-current protection of compressor 1
FP
Malfunction of DC motor
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...