GREE GMV5 HR HEAT RECOVERY UNITS
125
3.5.2 Restoring Factory Settings
Restoring Factory
Settings
Setting Method
Prompt for
Successful Settings
Remark
Restoring setting 1
Press and hold "SW8" on
the master unit for more
than 10 seconds.
All LEDs blink for
three seconds.
All factory settings of the ODU are restored
and the unit waits for re-commissioning.
Restoring setting 2
Press and hold "SW3"
and "SW8" on the master
unit for more than 10
seconds.
All LEDs blink for
five seconds.
Re-commissioning is not required. The number
of outdoor and IDUs is memorized. Addresses
of outdoor and IDUs are all cleared. All the
other function settings are cleared.
Restoring setting 3
Press and hold "SW5"
and "SW8" on the master
unit for more than 10
seconds.
All LEDs blink for
seven seconds.
Re-commissioning is not required. The number
of outdoor and IDUs is memorized. Addresses
of outdoor and IDUs retain the preceding
settings. All the other function settings are
cleared.
If above function settings are incorrect, unit will run abnormal and compressor may even be
damaged.
PART 2 COMMISSIONING PROCESS
NOTICE
!
①
It is forbidden to directly connect the compressor with power supply and forcibly power it on
during commissioning and maintenance.
②
Engineering commissioning operations must be performed on the GMV5 serial unit. Otherwise,
the unit cannot properly run.
③
Before commissioning is completed, the main board of ODU displays "module address 0F A0"
and that of IDU displays “A0”.
④
A module must be set to master module and only one can be set during commissioning.
⑤
An IDU must be set to master IDU and only one can be set during commissioning.
⑥
Other functions can use the factory settings if there are not special engineering requirements.
1 NECESSITY OF VRF ENGINEERING
COMMISSIONING
Different form ordinary air conditioning units, the VRF system raises high design requirements and
easily incurs operation-affected factors such as impurities and water during engineering installation. Due
to the requirements on engineering design/installation complexity and high-precise system control,
commissioning is mandatory after engineering installation. Only a qualified unit can be delivered for use.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...