Gree FP-102WM-D Скачать руководство пользователя страница 8

Floor Ceiling Tpye Fan Coil Unit

5

5.2 Selection of Installation location

(1)  Such a place where cool air can be distributed throughout room.
(2)  Such a place where condensation water is easily drained out.
(3)  Such a place that can handle the weight of the unit.
(4)  Such a place which has easy access for maintenance.
(5)  Such a place where is permitting easy connection with the chilling water pipe.
(6)  Such a place where is 1m or more away from other electric appliances such as television, 

audio device, etc.

(7)  

Avoid a location where there is heat source, high humidity or inflammable gas.

(8)  Be sure that the installation conforms to the installation dimension diagram.
(9)  The space around the unit is adequate for ventilation(Refer to Fig.2).
(10)  

The height of the installed location should be 2.3m or more from the floor.

INSTALLATION

PAPER PLANK

    

150cm or more

60cm or more

100cm or more

30cm or more

60cm or more

                                   Fig.1                                                                                 Fig.2

5.3 There are two types of installation

  

Ceiling type 

  

Floor type

Fig.3

Each type is similar to the other as follows:

(1)  Determine the mounting position on ceiling or wall.
(2)  Remove the return grill, the side panel, and suspender from 

the unit as per procedure below. Press the fixing knob of the 

return grilles, the grilles will be opened wider and then pull it 
out from the unit.

1)  Remove the side panel fixing screw and pull to the front 

direction(arrow direction) to remove(Refer to Fig.3).

2)  Loosen two hanger bracket setting bolts(M8) on each side 

for less than 10mm. Remove two hanger bracket fixing 
bolts(M6) on the rear side. Detach the hanger bracker by 
pulling backward (Refer to Fig.5).

(3)  set the suspension bolt (Use W3/8 or M10 size suspension bolts).

Adjust the distance from the unit to the ceiling slab beforehand (Refer to Fig.4).

(4)  Fix the hanger bracket to the suspension bolt.

Make sure that extended suspension bolt from the ceiling stays inside the arrowed position. 

Readjust the hanger bracket when it is outside the arrowed position (Refer to Fig.6) .

Содержание FP-102WM-D

Страница 1: ...D FP 102WM K BMS FP 34ZD K FP 51ZD K FP 68ZD K FP 85ZD K FP 102ZD K FP 136ZD K FP 170ZD K FP 204ZD K FP 136WM K BMS Thank you for choosing commercial air conditioners Please read this Owner s Manual c...

Страница 2: ...l DISPOSAL This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled w...

Страница 3: ...g 4 5 Installation 4 5 1 Dimension 4 5 2 Selection of Installation location 5 5 3 There are two types of installation 5 5 4 Electrical wiring 7 6 Drain Piping Work 8 7 Motorized valve 9 7 1 Installati...

Страница 4: ...or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety 2 Children sh...

Страница 5: ...le to blow all over the room Clean the air filter every week for higher efficiency by professional Close the window and door while operating the unit for saving energy Cover windows with a blind or a...

Страница 6: ...ecified capacity Do not use pieces of wire instead of fuse Do not insert objects into the air inlet or outlet when the air conditioner is running as it may cause damage or personal injury Also pay spe...

Страница 7: ...me coming out of the unit while running Hot air in the room mixes with cool air This causes smoke fume Inoperative remote control Loosened or disconnected wire between the unit and the display Check i...

Страница 8: ...more 60cm or more Fig 1 Fig 2 5 3 There are two types of installation Ceiling type Floor type Fig 3 Each type is similar to the other as follows 1 Determine the mounting position on ceiling or wall 2...

Страница 9: ...of the drain pipe slightly inclines to improve drainage Adjust the height by turning the nut with a spanner Insert the spanner from the hanger bracket opening Refer to Fig 8 Hanging installation It i...

Страница 10: ...sulated power cable used at 40 and resistible to 90 see GB T 16895 15 If the working condition changes they should be modified according to the related national standard Rubber bush Wiring clamp Power...

Страница 11: ...tely into the drain socket Tighten the clamp within the range of gray tape until the screw head is less than 4 mm from the hose Refer to Fig 12 13 5 Wrap the attached sealing pad OD over the clamp and...

Страница 12: ...uaranteed Flare nut Wiring interface Water outlet tube Torque wrench Thread fasten Spanner Valve Tape Water tube joint Fig 16 2 Both the tube joint and the motorized valve are G3 4 threaded Prior to t...

Страница 13: ...ould allow the condensate water to enter or damage the valve core and even form a short circuit which wouldresult in a fire hazard as Fig 20 Fig 20 The right way is placing the valve core in the prope...

Страница 14: ...function or damage the part Has the inlet and outlet been covered It may cause insufficient cooling or heating capacity 10 Test Operation wireless remoter controller 10 1 Before test operation 1 Do no...

Страница 15: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com...

Отзывы: