Floor Ceiling Tpye Fan Coil Unit

1

1 Operation Range

(1)  The operation pressure of the unit is no more than 1.6MPa. The entering water temperature 

for cooling shall be lower than 5°C, otherwise condensate would be caused on the unit. The 
entering water temperature for heating shall be not more than 70°C (normally 60°C), otherwise 
the cupper tube of the heat exchanger would be corroded. 

(2)  The ambient temperature range for cooling is 16-40°C and 10-35°C for heating. The relative 

humidity is equal or less than 95%.

(3)  It is a kind of comfort air conditioning unit, not applicable to be used under the locations with 

special requirements on corrosive, inflammable gas or heavy smog (like, kitchen), otherwise, 

the unit would fail to run properly or its service life would be shortened.

 2 Notices for operation 

(1)  This appliance is not intended for use by persons (including children) with reduced physical, 

sensory or mental capabilities, or lack of experience and knowledge, unless they have been 
given supervision or instruction concerning use of the appliance by a person responsible for 
their safety.

(2)  Children should be supervised to ensure that they do not play with the appliance.
(3)  If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a 

similarly qualified person in order to avoid a hazard.

(4)  An all-pole disconnection switch having a contact separation of at least 3mm in all poles should 

be connected in fixed wiring.

(5)  The appliance shall be installed in accordance with national wiring regulations.

3 Operating Guide

Only professional personnel could clean or replace the filter.
Before cleaning filter, the power must be cut off and wait until fan motor stops.

 

Remove  the air filter, clean it by a vacumm 

cleaner or if it is very dirty,wash it soap water, 
then wipe off unit it is completely dry before 
reinstalltion.

      

 

Clean the air conditioner and the remote 

control with dry cloth or a vacuum cleaner. If 
damp cloth is used, remove moisture by using 
cloth afterward.

       

Содержание FP-102WM-D

Страница 1: ...D FP 102WM K BMS FP 34ZD K FP 51ZD K FP 68ZD K FP 85ZD K FP 102ZD K FP 136ZD K FP 170ZD K FP 204ZD K FP 136WM K BMS Thank you for choosing commercial air conditioners Please read this Owner s Manual c...

Страница 2: ...l DISPOSAL This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled w...

Страница 3: ...g 4 5 Installation 4 5 1 Dimension 4 5 2 Selection of Installation location 5 5 3 There are two types of installation 5 5 4 Electrical wiring 7 6 Drain Piping Work 8 7 Motorized valve 9 7 1 Installati...

Страница 4: ...or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety 2 Children sh...

Страница 5: ...le to blow all over the room Clean the air filter every week for higher efficiency by professional Close the window and door while operating the unit for saving energy Cover windows with a blind or a...

Страница 6: ...ecified capacity Do not use pieces of wire instead of fuse Do not insert objects into the air inlet or outlet when the air conditioner is running as it may cause damage or personal injury Also pay spe...

Страница 7: ...me coming out of the unit while running Hot air in the room mixes with cool air This causes smoke fume Inoperative remote control Loosened or disconnected wire between the unit and the display Check i...

Страница 8: ...more 60cm or more Fig 1 Fig 2 5 3 There are two types of installation Ceiling type Floor type Fig 3 Each type is similar to the other as follows 1 Determine the mounting position on ceiling or wall 2...

Страница 9: ...of the drain pipe slightly inclines to improve drainage Adjust the height by turning the nut with a spanner Insert the spanner from the hanger bracket opening Refer to Fig 8 Hanging installation It i...

Страница 10: ...sulated power cable used at 40 and resistible to 90 see GB T 16895 15 If the working condition changes they should be modified according to the related national standard Rubber bush Wiring clamp Power...

Страница 11: ...tely into the drain socket Tighten the clamp within the range of gray tape until the screw head is less than 4 mm from the hose Refer to Fig 12 13 5 Wrap the attached sealing pad OD over the clamp and...

Страница 12: ...uaranteed Flare nut Wiring interface Water outlet tube Torque wrench Thread fasten Spanner Valve Tape Water tube joint Fig 16 2 Both the tube joint and the motorized valve are G3 4 threaded Prior to t...

Страница 13: ...ould allow the condensate water to enter or damage the valve core and even form a short circuit which wouldresult in a fire hazard as Fig 20 Fig 20 The right way is placing the valve core in the prope...

Страница 14: ...function or damage the part Has the inlet and outlet been covered It may cause insufficient cooling or heating capacity 10 Test Operation wireless remoter controller 10 1 Before test operation 1 Do no...

Страница 15: ...GREE ELECTRIC APPLIANCES INC OF ZHUHAI Add West Jinji Rd Qianshan Zhuhai Guangdong China 519070 Tel 86 756 8522218 Fax 86 756 8669426 E mail gree gree com cn www gree com...

Отзывы: