Ducted Type Split Air-Conditioner Units(Inverter Series)
2
2 Installation of Indoor Unit
2.1 Selection Proper Installation Location
(1) Avoid the direct sunshine.
(2) Make sure the suspension bracket is strong enough to withstand the unit’s weight.
(3) Select a place for easily connection of the drain hose.
(4) The inlet and outlet ports should not be obstructed so that the indoor air circulates well.
(5) Make sure the convenient connect of the connection pipes.
(6) Selection a location that is far away from the combustible or explosive material and gas.
(7) Selection a location that is far away from the cankerous material, fog, dusk or moist.
2.2 Outline Dimension and Installation Spots
Equip with an inspection hatch after lifting the unit. For the convenience of maintenance, the
service port should be on one side of the electric box and below unit’s lower level.
(1) Below are the outline dimension applicable to indoor units:
50/60kW
Fig.1
Below are dimensions of A, B, C, etc. for different models:
Unit: mm
Model
A
B
C
D
E
F
FGR50Pd/D(2)Na-M(I)
1980
1040
1120
1650
347
600
FGR60Pd/D(2)Na-M(I)
1980
1040
1120
1650
347
755
(2) Drill bolt holes and install bolts.
1) Stick the reference cardboard on the installation position; drill 4 holes according to the
hole site on the cardboard as shown in Fig 2; diameter of drilling hole is according to
the diameter of expansion bolt and the depth is 60-70mm(2-3/8~2-3/4 inch), as shown
in Fig 3.