Ducted Type Split Air-Conditioner Units(Inverter Series)
13
Selection of circuit breaker and power cord.
Model
Power supply
Circuit
breaker
capacity
(A)
Number of ground
wire × Min sectional
area (mm
2
)
Number of power
cord × Min sectional
area (mm
2
)
FGR25Pd/DNa-M(O)
380-415V 3N~ 50Hz
25
1×2.5
4×2.5
FGR30Pd/DNa-M(O)
380-415V 3N~ 50Hz
32
1×4.0
4×4.0
FGR50Pd/D(2)Na-M(I)
380-415V 3N~ 50Hz
10
1×1.5
4×1.5
FGR60Pd/D(2)Na-M(I)
380-415V 3N~ 50Hz
10
1×1.5
4×1.5
NOTES!
①
Selection of circuit breaker and power cord in the above table is based upon unit’s
maximum power (maximum current).
②
Specification of power cord is based on the working condition where ambient
temperature is 40
℃
and multi-core copper cable (working temperature is 90
℃
, e.g.
power cable with YJV cross-linked copper, insulated PE and PVC sheath) is lying on
the surface of slot. If working condition changes, please adjust the specification
according to national standard.
③
Specification of circuit breaker is based on the working condition where ambient
temperature of circuit breaker is 40
℃
. If working condition changes, please adjust
the specification according to national standard.
4 Check Items After Installation and Test Operation
4.1 Check Items After Installation
Check items
Possible conditions due to improper installation.
Check
Each part of the unit is installed securely?
Unit may drop, shake or emit noise.
Gas leakage test is taken or not?
Insufficient cooling (heating) capacity.
Unit gets proper thermal insulation or not?
There may be condensation and dripping.
Drainage is smooth or not?
There may be condensation and dripping.
Is the voltage in accordance with the rated
voltage specified on the nameplate?
Unit may have malfunction or components may get
damaged.
is the electric wiring and pipe connection
installed correctly?
Unit may have malfunction or components may get
damaged.
Unit is securely grounded or not?
Electrical leakage.
Power cord meets the required specification?
Unit may have malfunction or components may get
damaged.
Is the air inlet/outlet blocked?
Insufficient cooling (heating) capacity.
Length of refrigerant pipe and the charging
amount of refrigerant are recorded or not?
The refrigerant charging amount is not accurate.
Binding pieces on compressor feet are
removed or not?
Compressor may get damaged.