127
3.16.4 Selection of Air Switch and Power Cord
Model
Power Cord Size
Air Switch
apacity
(A)
Minimum Sectional
Area of
Ground Wire
(AWG)
Minimum Sectional
Area of Power
Cord
(AWG)
GMV-ND05T/E-T(U)
208/230V~,60Hz
15
AWG18
AWG18
GMV-ND07T/E-T(U)
208/230V~,60Hz
15
AWG18
AWG18
GMV-ND09T/E-T(U)
208/230V~,60Hz
15
AWG18
AWG18
GMV-ND12T/E-T(U)
208/230V~,60Hz
15
AWG18
AWG18
GMV-ND15T/E-T(U)
208/230V~,60Hz
15
AWG18
AWG18
GMV-ND18T/E-T(U)
208/230V~,60Hz
15
AWG18
AWG18
4 Installation of Connection Pipe
1
Conform to the following principles during pipe connection: Connection pipe should be as short as possible, so
is the height difference between indoor and outdoor units. Keep the number of bends as little as possible.
Radius of curvature should be as large as possible.
2
Weld the connection pipe between indoor and outdoor units. Please strictly follow the requirements for welding
process. Rosin joint or pin hole is not allowed.
3
When laying the pipe, be careful not to distort it. Radius of bending parts should be over 200mm (8inch). Note
that pipes cannot be repeatedly bent or stretched; otherwise the material will get harder. Do not bend or stretch
the pipe for more than 3 times at the same position.
4.1 Flaring Process
(1) Use pipe cutter to cut the connection pipe in case it is unshaped.
(2) Keep the pipe downward in case cutting scraps get into the pipe. Clear away the burrs after
cutting.
(3) Remove the flared nut connecting indoor connection pipe and outdoor unit. Then use flaring
tool to fix the flared nut into the pipe (as shown in Fig.4.1).
(4) Check if the flared part is flaring evenly and if there is any crack.
d1
d1
d2
d2
90°±1°
Fig. 4.1
4.2 Pipe Bending
(1) Reshape the pipe by hand. Be careful not to damage the pipe.
(2) Do not bend the pipe over 90°.
(3) If pipe is repeatedly bent or stretched, it will get hard and difficult to bend and stretch againch
Therefore, do not bend or stretch the bend for over 3 times.
(4) In case that direct bending will open cracks to the pipe, first use sharp cutter to cut the
insulating layer, as shown in Fig. 4.3. Do not bend the pipe until it is exposed. When bending is
done, wrap the pipe with insulating layer and then secure it with adhesive tape.
Содержание CM100N1480
Страница 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Страница 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Страница 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Страница 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Страница 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Страница 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Страница 266: ...JF00302921...