background image

■ 

HOLIDAY PROGRAM

An “8th day”, or Holiday program schedule may be entered for use

on holidays or vacation periods. More than one ON or OFF time may be
entered for the Holiday program.

A typical Holiday schedule may be to turn OFF at 12:01AM dur-

ing the holiday period.

1. Press 

Prog.

key to first free program

2. Press

key twice; OFF symbol

appears

3. Press 

h

key once to 12AM

4. Press 

m

key twice to 01

5. Press

key once

Enter additional ON or OFF schedules as above, followed by

the

key.

6. Press

key to enter Run Mode

■ 

IMPLEMENTING HOLIDAY PROGRAM

Up to 6 days in advance of the Holiday, the “8th day” or Holiday

schedule may be selected to begin on a certain day of the week, and
continue from 1 to 99 days.

Example: Thursday and Friday will be Holidays

1. Press

key once

2. Press 

Day

key to 4 (Th)   

3. Press 

Sel.

key twice to 02 

4. Press

key to enter Run Mode

Display will show

symbol above current time

8th day schedule will be implemented on Thursday and run for 2

days and then timer will revert back to normal programs.

Number
of Days

NOTE:

If 

Sel.

key is held down, it will scroll rapidly to 99 and back

to 01

To review the implementation scheduled, press

key once.

Display shows day of implementation and number of days holiday pro-

gram will be active. Press

key.

To delete the implementation scheduled, press

key twice. 

symbol disappears from display.

On the day the Holiday Program is selected to begin, the 8th day

program will be implemented. The display will show the Holiday symbol

and number of days remaining in the holiday period. To cancel at this

point, press

once.

■ 

TROUBLESHOOTING

PROBLEM: Days are flashing, pressing any key does nothing

except

key turns output ON and OFF. 

SOLUTION: 

Time of Day

and 

Day of Week 

have not been set. See

“SETTING THE TIME”

NOTE:

This is the condition after a reset. If the timer is found in this

condition after it has been installed, programmed and operating for a
while, it may indicate that electrical noise or voltage transients have dis-
rupted the microprocessor causing a loss of program information. Call 1-
800-272-1115 and request that a no-charge “Snubber Filter” be sent to
you to place across the input to the timer, which may solve the problem.

A second, but very unlikely cause of loss of program is a power fail-

ure with the backup battery low or dead. Check by disconnecting power
and monitoring how long the battery keeps the time of day in the display.

PROBLEM: Time of day was set while holding the

key down,

but days are still flashing.

SOLUTION: Current day of week was not set 

while holding down

the

key. 

See “SETTING THE TIME”

PROBLEM: It is 10AM and a ON program for 8AM was entered, but

the output is not ON. Display shows the

and

symbols.

SOLUTION: After programming, the timer does not “look back” to

determine if it should be ON. Press the

key (temporary override)

to turn the output ON; 

appears in display. The timer will

assume automatic operation at the next programmed event.

PROBLEM: A program for 8AM Monday thru Friday was entered,

but it will not accept it and CH1

is flashing.

SOLUTION: The ON

or OFF

was not entered as part of the

program. ON or OFF 

must be selected.

Printed in USA 082US 010.97

_____________________________________________________________________________________________________________________________________________________________________________

_____________________________________________________________________________________________________________________________________________________________________________

_____________________________________________________________________________________________________________________________________________________________________________

_____________________________________________________________________________________________________________________________________________________________________________

_____________________________________________________________________________________________________________________________________________________________________________

CH1

CH2

Holiday

Prog

ON/OFF

ON/OFF

h

m

Day(s)

Program

1

On

7 am

30

Mon., Tue., Wed., Thurs, Fri.

No

Digi 42/2 Program Schedules

GRÄSSLIN GmbH & Co. KG is ISO 9001 Certified

GRASSLIN CONTROLS CORPORATION

31 Industrial Ave. • Mahwah, New Jersey 07430 • Tel.: 201-825-9696 • Fax: 201-825-8694
E-mail: [email protected] • www.grasslin.com

Отзывы: