23

CURRENT (TORQUE) LIMIT ADJUST (CL)

(Clockwise Increases Current)

There are two methods for adjusting CL.

METHOD 1:

1 . Start the machine and run at desired speed, then apply

maximum load to the motor and turn CL trimpot fully

clockwise.

2 . Turn CL trimpot counterclockwise until the CL . (yellow) LED

lights and the machine starts to slow down.

3 . Turn the CL trimpot clockwise until the CL (yellow) LED just

turns off.

METHOD 2:

1 . Turn off AC power.

2 . Lock up the motor shaft, taking care not to cause damage.

3 . Connect a DC ammeter in series with the motor armature.

4 . Turn CL trimpot fully counterclockwise.

5 . Turn external speed pot fully counterclockwise.

6 . Turn on AC power and start control (CL (yellow) LED should

be on).

7 . Turn speed pot clockwise to about 1/3 speed setting.

8 . Adjust CL trimpot clockwise for desired motor current. (Do

not set for current greater than either the motor or control

nameplate rating).

9 . Turn off AC power, disconnect ammeter, and unlock motor

shaft. CL may be adjusted from O-150% of control rating.

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Содержание 176B1111

Страница 1: ...erutilized and idle equipment along with credit for buybacks and trade ins Custom engineering so your equipment works exactly as you specify Critical and expedited services Leasing Rentals Demos In st...

Страница 2: ...Installation Operation and Maintenance Manual Vari Speed S1000 Instruction Manual TRANSMISSIONS Inc Graham chnology Group Quality Instrumentation Guaranteed 888 88 SOURCE www...

Страница 3: ...chnology Group Quality Instrumentation Guaranteed 888 88 SOURCE www...

Страница 4: ...ic Block Diagram 1 4 Wiring 1 8 Verification Test 1 9 Component Location 2 1 Set Up Procedures 2 2 Two Speed Application 2 7 Troubleshooting Guide 2 8 Plug On Terminal Option 3 0 Available Options 3 1...

Страница 5: ...ate controller that converts single phase AC line power into an adjustable DC power source The unit has been designed to control permanent magnet PM or shunt wound DC motors from 1 20 to 2HP This NEMA...

Страница 6: ...ter 0 5V or 0 l0V input signal AC line switching for ON OFF with automatic ramp reset RUN STOP and INHIBIT control via external switches user supplied Status LED s for CURRENT LIMIT and RUN Plug In Cu...

Страница 7: ...ture 3 2 F to 131 F 0 C to 55 C Elevation Up to 3000 Feet 1000 meters without aerating NOTE The Ambient Temperature specification is referring to the environment surrounding the S1000 printed circuit...

Страница 8: ...ailable accessory Process Signal Input 0 5VDC or O 10VDC See Wiring and Warning on pg 16 Adjustments Minimum Speed 0 50 of motor base speed Maximum Speed 5 0 110 of motor base speed IR Compensation Ad...

Страница 9: ...horsepower to be used falls between two of the standard Current Sense Resistors use the higher values of the two Example 1 3 HP uses 1 2 HP Current Sense Resistor chnology Group Quality Instrumentatio...

Страница 10: ...9 DIMENSIONS chnology Group Quality Instrumentation Guaranteed 888 88 SOURCE www...

Страница 11: ...erious personal injury When using the higher horsepower units the optional 176B1122 heatsink is recommended to ensure the proper heat dissipation The 176B1122 provides 160 square inches This figure is...

Страница 12: ...ed for set up power should always be disconnected from the unit before any work is attempted 5 Do not apply AC line voltage to any terminals except L1 and L2 Failure to comply will cause permanent dam...

Страница 13: ...2 Motor overload protection must be provided by the equipment manufacturer or person installing controls per National Electrical Code chnology Group Quality Instrumentation Guaranteed 888 88 SOURCE ww...

Страница 14: ...ol s armature output off regardless of a RUN or Speed Command input As the INHIBIT circuit is activated any DECEL ramp the control is set for will be cancelled This allows the control s output and int...

Страница 15: ...compensation 5 Factory set for 1 2 second 6 Factory set for 1 2 second 7 If half wave field is required motor field windings are to be connected between F1 and L1 8 Factory set to accept 0 5 Vdc cut J...

Страница 16: ...15 chnology Group Quality Instrumentation Guaranteed 888 88 SOURCE www...

Страница 17: ...per J1 Jumper J1 is a 10K ohm 1 4 watt resistor which is located between the inhibit and SP2 terminals on the S1000 circuit board See Component Location page 21 for further information The two methods...

Страница 18: ...uld not be used as an Emergency Stop INHIBIT cannot override a catastrophic drive failure A system Emergency Stop function necessary to protect personnel or equipment will always remove AC power from...

Страница 19: ...the motor requires a 100 VDC filed follow the procedure outline above 3 Refer to Ratings Chart pg 8 for appropriate Current Sense Resistor size that is needed depending upon the horsepower of motor t...

Страница 20: ...edures because the line voltage will be present on the power and motor terminals as well as on the printed circuit board when power is on See the Component Location pg 8 to identify parts referenced d...

Страница 21: ...ch in the RUN position The RUN green LED should glow but the motor should not turn If LED does not come on verify that INHIBIT is not activated 4 Slowly rotate Speed Pot in a clockwise direction Motor...

Страница 22: ...21 COMPONENT LOCATION chnology Group Quality Instrumentation Guaranteed 888 88 SOURCE www...

Страница 23: ...INGS MIN SPEED Zero volts MAX SPEED 90VDC Output for 120 VAC line 180VDC Output for 240 VAC line Current Limit CL 100 of Control Rating IR Compensation Set for no compensation ACCEL Minimum DECEL Mini...

Страница 24: ...ck up the motor shaft taking care not to cause damage 3 Connect a DC ammeter in series with the motor armature 4 Turn CL trimpot fully counterclockwise 5 Turn external speed pot fully counterclockwise...

Страница 25: ...d i e hand held tachometer 1 Set motor speed to 1 2 of base speed rating 2 Load motor to 100 of nameplate rating motor speed will decrease 3 Turn IR clockwise until motor speed returns to original unl...

Страница 26: ...ps turning This will give the best motor speed linearity MIN SPEED may be adjusted from O to 50 of motor s rated base speed MAXIMUM SPEED ADJUSTMENT MAX Clockwise Increases Maximum Speed 1 Produce a R...

Страница 27: ...for desired times Both ACCEL and DECEL trim pots adjust from a linear 5 to 15 seconds Acceleration rate may be extended with CL if reflected inertia is high DECEL may be longer if reflected inertia i...

Страница 28: ...2 With SPDT contacts closed between terminals SP2 and SP3 adjust the MIN SPEED trimpot to desired low speed 3 With SPDT contacts closed between terminals SP1 and SP2 adjust the MAX SPEED trimpot to d...

Страница 29: ...operly 6 Unit is in Current torque Limit Check CL yellow LED if lit this indicates that CL pot is set too low or motor is overloaded 7 With power removed from unit and motor leads disconnected check f...

Страница 30: ...nge trimpot with isolated units Rotate trimpot clockwise to increase speed 2 Unit is in Current torque Limit Check CL yellow LED if lit this indicates that CL pot is set too low or motor is overloaded...

Страница 31: ...al wiring NOTE Wiring to Terminal Board before installation to Vari Speed S1000 may simplify procedure 2 Carefully plug on the Terminal Board to the Vari Speed S1000 making sure that all connectors ar...

Страница 32: ...1122 For use in higher horsepower applications P o t e n t i o m e t e r K i t 176B1121 Includes a 5k ohm 1 W pot and mounting hardware Knob and dial plate are also available separately Current Sensor...

Страница 33: ...all not be paid by Graham Transmissions Inc If defects occur within the above mentioned periods the product shall be forwarded to Graham Transmissions Inc insurance and freight prepaid by customer Bef...

Страница 34: ...ed of merchantability or fitness for a particular purpose Graham Transmissions Inc neither assumes nor authorizes any other person firm or corporation to assume for it any other liability in connectio...

Страница 35: ...chnology Group Quality Instrumentation Guaranteed 888 88 SOURCE www...

Страница 36: ...chnology Group Quality Instrumentation Guaranteed 888 88 SOURCE www...

Страница 37: ...N93 W14575 Whittaker Way Menomonee Falls WI 53051 888 363 1313 TRANSMISSIONS Inc Graham 01 00 Revision A 176R0104 chnology Group Quality Instrumentation Guaranteed 888 88 SOURCE www...

Страница 38: ...uipment Have surplus equipment taking up shelf space We ll give it a new home Learn more Visit us at artisantg com for more info on price quotes drivers technical specifications manuals and documentat...

Отзывы: