Integration
333587D
79
Automation Outputs
NOTE:
Print the following tables in color.
A Used for ambient map 18E218.
H Additional to ambient map for heated map 18E224.
Color Coded Key
Active Pump Only
Active (Ram Unit) or Inactive
(Tandem Unit) Pump
Heat 1 for Pump 1
Heat 2 for Pump 2
E-Flo iQ Maps 18E218 and 18E224
Automation OUTPUTS (signal from PLC to E-Flo iQ)
Instanc
e ID
Description
Data
Type
Min
Value
Max
Value
Bit
Byte
Heat
1
SYS - Data Exchange Element Command
uint16
0
32767
0-14
0-1
A
2
System Enable/Remote Start Request
Boolean
0
1
0
2
A
3
System Disable Request
Boolean
0
1
1
A
4
Pump PLC Lockout/Control Request
Boolean
0
1
2
A
5
Style Enable Request
Boolean
0
1
3
A
6
Go Signal Request
(use discrete signal for proper timing!)
Boolean
0
1
4
A
7
Dispense Complete Request
Boolean
0
1
5
A
8
Tandem Crossover Request
Boolean
0
1
6
A
9
Prime Pump Request
(Tandem Unit sent to Inactive Pump)
(Ram Unit sent to Active Pump)
Boolean
0
1
7
A
10
Valve Depressurization Request
Boolean
0
1
0
3
A
11
Platen Depressurization Request
Boolean
0
1
1
A
12
Auto Depressurization Cancel Request
Boolean
0
1
2
A
13
Acknowledge / Clear Errors Request
(both pumps)
Boolean
0
1
3
A
14
Reserved Bit 1
Boolean
-
-
4
A
15
Reserved Bit 2
Boolean
-
-
5
A
16
Reserved Bit 3
Boolean
-
-
6
A
17
Reserved Bit 4
Boolean
-
-
7
A
18
Desired Style Number Request
uint16
0
16
0-14
4-5
A
19
Style Fieldbus Pre-charge Target
(xxx.x bars)
uint16
0.0
413.6
0-14
6-7
A
20
Style Fieldbus Flow-rate Target
(xxxx cc/min)
uint16
0
6000
0-14
8-9
A