Setup
Setup
Setup Screen
Screen
Screen 7:
7:
7: Pressure
Pressure
Pressure
Use this screen to set your pressure maximum and
minimum alarm values, and to select your preferred
units.
Key
Key
Key
Enter the screen to set or change
preferences.
Press to activate a field for editing or
to accept the highlighted selection on a
menu.
Move to the right when editing number
fields. Press again to accept the entry
when all digits are correct.
Set your desired maximum (first data
field) and minimum (second data field)
pressure. Pressures outside of these
parameters will trigger an alarm.
Select (
) if you want the alarm to be
based on percent deviation from the
current active target pressure. When
selected, the maximum and minimum
values shown will automatically update
based on the se/- percentage
and the current active target pressure on
the Run screen.
Key
Key
Key
Set the +/- percent difference from the
pressure target that will trigger an alarm.
Alarm Auto Clear Enable. If enabled,
when the pressure returns to within the
pressure limit set points, the pressure
alarm will clear on the screen and on
any attached accessories such as a light
tower.
Select the type of alarm.
Advisory. System does not shut down.
It does not attempt to modify operation.
Event is logged.
Deviation. System does not shut down.
It may attempt to modify operation to
adjust to the conditions. Event is logged.
Alarm. System shuts down. Event is
logged.
Exit data editing.
Move between Setup Screens, fields on
a screen, or to increment/decrement the
digits when editing number fields.