Goulds AQUAVAR CPC Скачать руководство пользователя страница 1

AQUAVAR® CPC

Centrifugal Pump Controller

Quick Start Guide

Overview

The installation of the AQUAVAR CPC adjust-
able speed drive follows the outline below.

Task

PREPARE for installation

UNPACK the drive

PREPARE mounting location

REMOVE the front cover

MOUNT the drive

INSTALL wiring

CHECK installation

REINSTALL the cover

APPLY power

START-UP Wizards

Application

This guide provides a quick reference for 

installing Aquavar CPC drives having a 

standard enclosure (NEMA 1).
NOTE: This guide does not provide 

detailed installation, safety or operational 

instructions. See the Installation Operation 

Manual for complete information.

Prepare for Installation

WARNING! The Aquavar should ONLY 
be installed by a qualified electrician.

Check

• Motor Compatibility – Motor type, nominal current, 

frequency and voltage range must match drive 

specifications (3 phase motor only).

• Suitable Environment – Drive requires heated, 

indoor controlled environment that is suitable for 

the selected enclosure.

• Wiring – Follow local codes for wiring and fusing 

requirements. Refer to NEC.

Refer to the Installation Operation Manual and 

confirm that all preparations are complete.

Tools Required

Screwdrivers, wire stripper, tape measure, 

mounting screws or bolts, and drill.
Use the following chart to interpret the type code 

found on the drive label.

Collect Motor Data

Collect the following data from the motor name-

plate for later use in the Aquavar startup:

• Voltage ______________________________
• Nominal Motor Current _______________
• Nominal Frequency ___________________
• Nominal Speed ______________________
• Nominal Power _______________________

Unpack the Drive

NOTE: Lift the Aquavar by its chassis and not by 
its cover.

1. Unpack the drive.
2. Check for any damage and notify the 

shipper immediately if damaged com-

ponents are found. 

3. Check the contents against the order 

and the shipping label to verify that all 

parts have been received.

Prepare the Mounting Location

The drive requires a smooth, 
vertical, solid surface, free from 
heat and moisture, with free 
space for air flow – 200 mm (8 
in.) above and below, and 25 
mm (1 in.) around the sides of 
the drive.

1. Mark the mounting 

points.

2. Drill the mounting holes.

Remove the Front Cover

1. Remove the control panel  

(display), if attached.

2. Loosen the  

captive screw 
at the top.

3. Pull near the 

top to remove 
the cover.

Mount the Drive

1. Position the  

AQUAVAR and use 
screws or bolts to  
securely tighten all 
four corners.

2. Attach a warning 

sticker in the  
appropriate language 
on the inside plastic shell.

Install the Wiring

1. Install thin-wall conduit clamps (not 

supplied) in the conduit/gland box.

2. Install conduit/gland box.

Wiring Power

1. Connect conduit runs to box.
2. Route input power and motor  

wiring through conduits.

1

X0002

 

CPC  4  370 1

AQUAVAR

®

 (Series)

Voltage

 

2 – 230 Volt 

4 – 460 Volt

Amps

 

370 Amps 

*See Technical Section

NEMA Enclosure Rating

 

1 – NEMA 1 

2 – NEMA 12

 

3 – NEMA 3R with disconnect

 

4 – NEMA 4 with disconnect

 

5 – NEMA 3R without disconnect

 

6 – NEMA 4 without disconnect

Options

A – Field Bus Card 

(Devicenet, Profibus)

* Consult factory for other options, if available.  

Not all combinations may be available.

3. Strip wires.
4. Connect power, motor and  

ground wires to the drive terminals. 

See “Power Connections” in the 

instruction manual.

Frame Sizes R1…R4

* Single phase input power must use U1, W1 

and PE for wiring.

WARNING! For floating networks 

remove screws at EM1 and EM3 on 

Frame Sizes R1…R4.

Frame Size R5

Frame Size R6

WARNING!  
For floating 

networks remove  
screws at F1 and 
F2 on Frame Sizes  
R5 or R6.

QUICKSTART GUIDE

AQCPCQR

Отзывы: