Components and Operation
English, Revision 04, Date: 19.01.2015
19
Table of the data words of a telegram with 21 byte length.
Byte #
Length
Value
Type
Description
1
1 Byte
0x0000.0001
ASCII-061 : „=“
Start pulse (Default: „=“)
2,3
2 Byte
0x0000.0002
signed short
Y-Position: Y [mm] (lateral deviation)
within the range of -750 .. 0 .. +750
In case of an invalid value (no Transponder
detected) = 32767 *)
4,5
2 Byte
0x0000.0004
signed short
X-Position: X [mm] (longitudinal deviation)
within the range of -300 .. 0 .. +300
In case of an invalid value (no Transponder
detected) = 32767 *)
6,7
2 Byte
0x0000.0008
unsigned short
16 bit Transponder code
8,9
2 Byte
0x0000.0010
signed short
Voltage generated by the transponder in the
reference coils in [units]
10,11
2 Byte
0x0000.0020
unsigned short
voltage generated by the Transponder in the
positioning coils in [units]
12
1 Byte
0x0000.0040
unsigned char
operational voltage for the Antenna [100 mV]
13
1 Byte
0x0000.0080
unsigned char
power consumption [10 mA]
14
1 Byte
0x0000.0100
signed char
temperature within the antenna [
o
C]
15
1 Byte
0x0000.0200
unsigned char
number of readings during the latest Transpon-
der crossing
16,17
2 Byte
0x0000.0400
unsigned short
receiver frequency [10 Hz]
18,19
2 Byte
0x0000.0800
unsigned short
transmitter frequency [10 Hz]
20, 21
2 Byte
0x0000.1000
unsigned short
system status in binary encoding
(22)
1 Byte
unsigned char
check sum, only in transparent protocol!
XOR operation of all bytes including the start
character.
*) = In case that either the position for x or y exceeds its valid range,
both
values are set to 32767.
Table 2
Data words in a telegram with 21 byte length