![Gossen MetraWatt U1601 Скачать руководство пользователя страница 72](http://html.mh-extra.com/html/gossen-metrawatt/u1601/u1601_operating-instructions-manual_2247120072.webp)
72
Gossen Metrawatt GmbH
If a parameters configuring error is detected:
For U1660: Check METER CONSTANT
For U1661: Check LONFACTOR, LONOFFSET and P-FACTOR.
Start reinstallation:
At the control panel: by changing the neuron ID. For example, set the first digit to 1,
and then back to 0.
Reinstallation of all channels can be initialized via SETUP / LON / INSTALLATion.
At terminal window: For one channel with the following command
LonRE c = 1
For all channels with the following command
LonRE ** = 1
Repeat this procedure until the device type is recognized.
12.7
Additional LON Parameters
• Waiting time for responses:
SETUP / LON / TIMING CODE = 9 (
LONSTATTIMing = 9
)
Waiting time is set for a response with TIMING CODE.
TIMING CODE is an encoded value for the duration of
time allowed between a query and a response. The
default setting (9) should only be changed by experts!
• Time between two queries:
A delay can be selected here in order to reduced data
traffic in the bus.
SETUP / LON / POLL DELAY = 0 (
LonPOLLDELay = 0
)
POLL DELAY is time between queries from 2 channels
in milliseconds.
Example:
POLL DELAY = 300, 60 channels:
all channels are queried in 18 seconds.
Default:
POLL DELAY = 0, 60 channels:
all channels are queried in 5 seconds.
12.8
Channel Errors
The following channel errors may occur depending upon the type of installed device:
1)
Only for U1661 B2 4 ... 20 mA
Bit
U1601 Description A2000
DME400 U1660
U1661
U1681
U1687
U1689
OCL21
0
U1281
U1381
U1289
U1387
U1389
EM228x
EM238x
1 Communications error
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
2 Unknown device
✔
✔
✔
3 Self-test error
✔
✔
✔
✔
✔
✔
✔
4 Calibration error
✔
✔
✔
6 Off-line
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
9 Broken sensor
✔
1)
✔
✔
✔
10 Phase failure
✔
✔
✔
✔
✔
11 Phase sequence error
✔
✔
✔
✔
12 Overflow
✔
✔
✔
✔
✔
✔
✔
✔
25 Parameter configura-
tion error
✔
✔
TIMING-CODE
Waiting time in ms
LONSTATTIMing
0
16
1
24
2
32
3
48
4
64
5
96
6
128
7
192
8
256
9
384
10
512
11
768
12
1.024
13
1.536
14
2.048
15
3.072
Содержание U1601
Страница 1: ...U1601 U1602 U1603 Summators Energy Control System ECS 3 348 869 03 15 1 21 Operating Instructions ...
Страница 11: ...Gossen Metrawatt GmbH 11 ECS LAN Sample Network ...
Страница 73: ...Gossen Metrawatt GmbH 73 13 Functions Overviews Functions Overview U1601 ...
Страница 74: ...74 Gossen Metrawatt GmbH Functions Overview U1602 ...
Страница 75: ...Gossen Metrawatt GmbH 75 Functions Overview U1603 ...
Страница 79: ...Gossen Metrawatt GmbH 79 ...