Start reinstallation:
By changing the neuron ID. For example, set the first digit to 1, and then back to 0.
Reinstallation of all channels can be initialized via SETUP / LON / INSTALLATion.
Repeat this procedure until the device type is recognized.
12.5
Configuration at a PC with ECSwin Software
• Log on to the desired summator at the terminal.
• Access the “Configure / Channel parameters” menu function.
• Wait until all data have been read in.
• Enter all parameters to the “Meter inputs” index register.
– MConst is transmitted to the device for the U1660 (double check).
– P-FACTOR is transmitted to the device for the U1661 (double check).
• Enter all parameters to the “LON parameters” index register.
– The LON factor and LON offset parameters are transmitted to the device for the
U1661, (double check).
• Transmit data to the summator.
• Data are read back automatically and the LONtype column is filled in (this column has
read-only access). Due to the fact that type recognition via the LON bus takes several
seconds, “???????.?” is sometimes displayed as a type designation. The channel
parameters window should then be exited and reopened.
• Check LON type.
If the type is displayed correctly: Check for channel errors.
Installation is now complete.
If the connected device is not displayed at LON type: Check the LON ID.
If LON type is ??????.?: Check the LON ID, and check LON wiring.
Start reinstallation:
Use the following command for a single channel: LonRE c = 1 in terminal window
Use the following command for a all channels: LonRE ** = 1
Repeat this procedure until the device type is recognized.
12.6
Replacing a LON Device
• Deactivate the affected summator channel
(control panel: MODE = OFF; ECSwin: CMode = 0).
Deactivate all affected channels for multi-channel devices.
• Replace the LON device.
• Enter a new LON ID.
• Reactivate all deactivated channels
(control panel: MODE = LON; ECSwin: CMode = 4).
• Check LON type.
If the type is displayed correctly: Check for channel errors.
Replacement is now complete.
If the connected device is not displayed at LON type: Check the LON ID.
If LON type is ??????.?: Check the LON ID, and check LON wiring.
Parameters are transmitted to the device in the case of the U1660 and the U1661.
Check for parameters configuring errors. Control panel: CHANNEL ERROR menu,
terminal: ErrChan c
Содержание U1601
Страница 1: ...U1601 U1602 U1603 Summators Energy Control System ECS 3 348 869 03 15 1 21 Operating Instructions ...
Страница 11: ...Gossen Metrawatt GmbH 11 ECS LAN Sample Network ...
Страница 73: ...Gossen Metrawatt GmbH 73 13 Functions Overviews Functions Overview U1601 ...
Страница 74: ...74 Gossen Metrawatt GmbH Functions Overview U1602 ...
Страница 75: ...Gossen Metrawatt GmbH 75 Functions Overview U1603 ...
Страница 79: ...Gossen Metrawatt GmbH 79 ...