![Gossen MetraWatt U1601 Скачать руководство пользователя страница 64](http://html.mh-extra.com/html/gossen-metrawatt/u1601/u1601_operating-instructions-manual_2247120064.webp)
64
Gossen Metrawatt GmbH
12.3
Device Descriptions
12.3.1 A2000 Multifunctional Power Meter
Energy and Power Function
Settings:
CMODE k = 4 LON
. Desired energy is selected by means of the network variable
number under LonCHANNEL.
LonCHANNEL k = Nv#
. The displayed unit of
measure is the power unit of measure. Only the energy network variable is entered,
and corresponding power is read out automatically.
Energy Values and Corresponding Power
Only the LTHT setting is supported by the A2000 (default status).
Analog Value Function
All other network variables can be read in as analog values.
Settings:
CMODE k = 5 LonA
. The desired value is selected by means of the network
variable number under LonCHANNEL.
LonCHANNEL k = Nv#
. The displayed unit of measure is the power unit of
measure.
12.3.2 DME400 Programmable Multi-Transducer
LON Settings:
Domain 1:
Length 1, ID 00
Node state:
Configured, online
Energy and Power Function
Settings:
CMODE k = 4 LON
. Desired energy is selected by means of the network variable
number under LonCHANNEL.
LonCHANNEL k = Nv#
. The displayed unit of
measure is the power unit of measure. Only the energy network variable is entered,
and corresponding power is read out automatically.
Energy Values and Corresponding Power
Only this setting is supported (must be configured).
Nv#
Name
Description
Nv#
Name
Description
51
NvoWHTotExpLT
Active energy export LT
27
nvoWatTot
Active power in the network
52
NvoWHTotImpLT
Active energy import LT
27
nvoWatTot
Active power in the network
53
NvoWHTotExpHT
Active energy export HT
27
nvoWatTot
Active power in the network
54
NvoWHTotImpHT
Active energy import HT
27
nvoWatTot
Active power in the network
58
NvoVarHTotExpLT
Reactive energy export LT
35
nvoVarTot
Reactive power in the network
59
NvoVarHTotImpLT
Reactive energy import LT
35
nvoVarTot
Reactive power in the network
60
NvoVarHTotExpHT
Reactive energy export HT
35
nvoVarTot
Reactive power in the network
61
NvoVarHTotImpHT
Reactive energy import HT
35
nvoVarTot
Reactive power in the network
Nv#
Name
Description
Nv#
Name
Description
51
Nvo_EnergyA
Active energy export
27
nvo_TrueSY_Power
Active power in the network
52
Nvo_EnergyB
Active energy import
27
nvo_TrueSY_Power
Active power in the network
53
Nvo_EnergyC
Inductive reactive energy
35
nvo_ReactSY_Pwr
Reactive power in the network
54
Nvo_EnergyD
Capacitive reactive energy
35
nvo_ReactSY_Pwr
Reactive power in the network
Содержание U1601
Страница 1: ...U1601 U1602 U1603 Summators Energy Control System ECS 3 348 869 03 15 1 21 Operating Instructions ...
Страница 11: ...Gossen Metrawatt GmbH 11 ECS LAN Sample Network ...
Страница 73: ...Gossen Metrawatt GmbH 73 13 Functions Overviews Functions Overview U1601 ...
Страница 74: ...74 Gossen Metrawatt GmbH Functions Overview U1602 ...
Страница 75: ...Gossen Metrawatt GmbH 75 Functions Overview U1603 ...
Страница 79: ...Gossen Metrawatt GmbH 79 ...