Data Interface
Refer to operating instructions 3-349-204-15 for detailed information regarding the data interface.
Mechanical Installation / Preparation
Figure 1, Housing Dimensions and Panel Cutout
The R2900 controller is intended for installation to a control panel.
The installation location should be vibration-free to the greatest
possible extent. Aggressive vapors shorten the service life of the
controller. Requirements set forth in VDE 0100 must be observed
during the performance of all work. Work on the device may only
be carried out by trained personnel who are familiar with the dan-
gers involved.
Set the housing into the panel cutout from the front, and secure it
from behind at the left and right-hand sides with the two included
screw clamps. Typical tightening torque amounts to 10 Ncm, and
a value of 20 Ncm should not be exceeded.
In general, unobstructed air circulation must be assured when one
or several devices are installed. The ambient temperature under-
neath the devices may not exceed 50
°
C.
5
96
96
50
5
70
Variants
A1 ... A6, D0, F0
Variant A7, A8 or D1, or
F1
92
+0,8
92
+0.8
Panel Cutout