GMC-I Messtechnik GmbH
R2700–43
Data Logger
•
The data logger has enough capacity for 3600 sampled value pairs including actual values and manipulated variables. The logger sampling cycle
can be configured within a range of 0.1 to 300.0 seconds. This results in recording times of 0.1 to 300 hours (6 minutes to 12 days).
•
Recording must be started over again each time the device is reset, and data are lost if auxiliary power fails.
•
Recording can be started via a binary input, with the setting
LoGG = YES
in the configuration or via interface.
•
After the ring buffer has been filled to capacity with 3600 entries, the oldest values are deleted as new ones are recorded.
•
Entries can only be read out via the bus interface or the infrared interface. See the interface description for detailed information.