
45
Example:
Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons
2. Determine the proper air flow for the cooling system. Most
cooling systems are designed to work with air flows between
350 and 450 CFM per ton. Most manufacturers recommend an
air flow of about 400 CFM per ton.
Example:
2.5 tons X 400 CFM per ton = 1000 CFM
The cooling system manufacturer’s instructions must be checked
for required air flow. Any electronic air cleaners or other devices
may require specific quantity of air, consult installation instruc-
tions of those devices for requirements.
3. Knowing the furnace model, locate the high stage cooling air
flow table. Look up the cooling air flow determined in step 2
and find the required cooling speed and adjustment setting.
Example:
A *MVM970603BN furnace installed with a 2.5 ton
air conditioning system. The air flow needed is
1000 CFM. Looking at the cooling speed chart for
*MVM970603BN, find the air flow closest to 1000
CFM. A cooling airflow of 1000 CFM can be
attained by selecting the cooling speed “C” and
the adjustment to “normal”.
4. Continuous fan speed is selectable at 25%, 50%, 75% or 100%
of the furnace’s maximum airflow capability.
Example:
If the furnace’s maximum airflow capability is 2000
CFM, the continuous fan speed at 25% will be 0.25
x 2000 or 500 CFM.
5. Locate the blower speed selection DIP switches on the integrated
control module. Select the desired “cooling” speed tap by
positioning switches 1 and 2 appropriately. Select the desired
“adjust” tap by positioning switches 9 and 10 appropriately.
Refer to the DIP switch chart for switch positions and their
corresponding taps. Verify CFM by noting the number displayed
on the dual 7-segment LED display.
6. The multi-speed circulator blower also offers several custom ON/OFF ramping profiles for cooling. These profiles
may be used to enhance cooling performance and increase comfort level. The ramping profiles are selected using DIP
switches 7 and 8. Refer to the bullet points below for a description of each ramping profile. Verify CFM by noting the
number displayed on the dual 7-segment LED display.
•
Profile A
provides only an OFF delay of one (1) minute at 100%
of the cooling demand airflow.
•
Profile B
ramps up to full cooling demand airflow by first
stepping up to 50% of the full demand for 30 seconds. The
motor then ramps to 100% of the required airflow. A one (1)
minute OFF delay at 100% of the cooling airflow is provided.
Model
Tap
Low
Stage
Cool
High Stage
Cool
100%
Heat
*CFM
Low heat
CFM for
2 stage
A
398
599
953
667
B
557
817
1059
740
C
696
1007
1158
808
D
810
1212
1260
881
A
403
629
1202
855
B
540
806
1316
923
C
705
1023
1389
1033
D
819
1230
1396
1063
A
513
789
1228
867
B
660
967
1337
939
C
791
1182
1430
1016
D
913
1375
1516
1077
A
564
820
1818
1256
B
784
1133
1870
1292
C
982
1464
1910
1316
D
1259
1736
1957
1358
A
547
867
1891
1329
B
831
1160
1940
1362
C
1020
1467
1968
1390
D
1278
1910
2028
1440
A
433
656
938
687
B
541
790
950
751
C
686
972
986
814
D
806
1195
992
874
A
405
624
1057
758
B
549
808
1146
815
C
678
994
1256
882
D
784
1177
1349
946
A
556
837
1234
889
B
714
1022
1325
944
C
838
1206
1442
1019
D
991
1475
1528
1068
A
524
784
1759
1209
B
744
1078
1797
1249
C
927
1388
1840
1277
D
1185
1766
1881
1300
*100% CFM sho wn. CFM will vary pro po rtio nally with the gas valve B TU/H input.
*CVM970803BN
*CVM970804CN*
*CVM971005CN*
*MVM971005CN*
*MVM971205DN*
*CVM970603BN
*MVM970603BN*
*MVM970803BN*
*MVM970804CN*
50% CFM
1/2 min
100% CFM
100% CFM
1 min
OFF
OFF
Figure 52B
OFF
100% CFM
100% CFM
1 min
OFF
Figure 52A