Leak alarm type LWG 2000
part no. 15 073 57 c
13 / 16
TECHNICAL DATA
Display unit
electrical device acc.
EN 60335-1
•
over-voltage caterogy III
•
contamination degree 2
•
protection class type I
Supply voltage
230 V AC 50 to 60 Hz
Power consumption
2.5 VA
Sound level of buzzer
≥ 70 dB(A)
Dimensions H/W/D in mm
120 x 120 x 50
Voltage tolerance
+10 % / -15 %
Housing
Polyester
Ambient temperature
-20 °C to +60 °C
Type of protection
IP30 acc. to EN 60529
Probe
Voltage
12 V DC
Material
Stainless steel 1.4301
Probe length
2m, 5m, 20m
Tank installation Probe length maximum 1.4 m
Length of probe cable
3.6 m
Storage medium temperature -20 °C to +60 °C
Ambient temperature
-20 °C to +60 °C
Switching and reset times
Switching
time
according to
EN 13160-4:
The time that the leak alarm needs to indicate the presence of stored
operating medium when the level increases by a specified value.
Water
10 minutes, 58 seconds
Fuel oil
7 minutes, 49 seconds
FAME
8 minutes, 55 seconds
Reset time
according to
EN 13160-4:
The time that the leak alarm needs from displaying the stored operating
medium to reach the initial status without any stored operating medium
Water
41 seconds
Fuel oil
1 minute, 25 seconds
FAME
13 seconds
TECHNICAL CHANGES
All the information contained in this assembly and operating manual is the result of product
testing and corresponds to the level of knowledge at the time of testing and the relevant
legislation and standards at the time of issue. We reserve the right to make technical changes
without prior notice. Errors and omissions excepted. All figures are for illustration purposes
only and may differ from actual designs.