Caramatic DriveTwo
18 / 72
Artikel-Nr. 71 825 50
Installation position
Vertical version
Horizontal version
Incorrect
To ensure the correct function, the Caramatic DriveTwo safety gas pressure regulation
device must:
•
be tightly screwed onto a stable wall / ceiling (with 2 screws – not included),
•
be installed vertically on a stable wall or horizontally on the ceiling of the gas cylinder crate,
depending on the version,
•
the trigger element must always sit in a vertical position (see arrow above),
•
the installation direction must be observed. This is indicated by an arrow on the safety gas
pressure regulation device.
Correct
Incorrect
The automatic changeover valve must be installed so that the hose connections are at the
highest position; at least above the cylinder valve.
To prevent re-liquefied gas getting into the regulator, this pressure regulator may not be
installed lower than the tank or cylinder valve. Pipes and hoses that are connected to the
inlet connector of the pressure regulator must have a constant downward incline to the tank
or cylinder.