Set-up 6
0020300875_01 Energy
7
Installation and maintenance instructions
19
6.7.4
Flue Configuration Description
6.7.4.1 Horizontal Concentric Flue
⌀
60/100 mm or
⌀
80/125 mm (C13 type installation)
1
1
Gasket (fitted)
Note
If the terminal is at less than 1.80 m from the
ground, you must install a terminal protection kit.
Type
Max. length (L)
Height (H)
60/100 diameter
10 m
76 mm
80/125 diameter
25 m
169 mm
Each time an additional 90° bend is necessary (or 2 at 45°),
the length (L) must be reduced by 1 m.
6.7.4.2 Vertical Concentric Flue
⌀
60/100 mm or
⌀
80/125 mm (C33 type installation)
Consult the separate installation manual for air/flue gas sys-
tems supplied with your appliance for all possibilities and as-
sociated accessories and how to install the flue system.