GENERAL DESCRIPTION

The Globe Series GL-QR/DC sprinklers are listed Quick 

Response domed concealed sprinklers which utilize a 3mm 

frangible glass bulb as the thermosensitive operating ele-

ment. They are Listed and Approved as Standard Cover-

age sprinklers and are to be installed in accordance with 

the guideline of the appropriate Installation Standard being 

mandated by the AHJ (i.e. NFPA 13). While providing addi-

tional aesthetic appeal from that of a semi-recessed sprin-

kler, the GL-QR/DC additionally provides a 1/2” of total ad-

justment. The sprinkler is available in five temperatures and 

the domed cover plate is available in two temperatures. An 

optional protective cap (P/N 327119) can be ordered to pre-

vent ceiling installation damage to the sprinkler. The protec-

tive cap is removed and the cover plate is installed when the 

system is ready for service. See “Installation” steps within 

this document.

OPERATION

The soldered cover plate drops off the retainer assembly 

when  exposed  to  heat,  as  from  a  fire,  that  has  reached 

the plate’s Listed temperature rating, exposing the sprin-

kler above. As heat encompasses the glass bulb operating  

element of the sprinkler, the fluid in the bulb expands, com

-

pressing the air bubble within the bulb. When the air bubble 

can no longer compress, the fluid expansion causes break

-

age of the glass bulb, resulting in release of the water seat  

assembly and discharge of water from the sprinkler.

TECHNICAL DATA

SIN

• 

GL2845, GL4245, GL5645, GL8145

Approvals

• 

cULus Listed

Maximum Working Pressure

• 

175 psi (12 bar)

• 

Factory tested to 500 psi (34 bar)

Minimum Operating Pressure

• 

7 psi (48 kPa)

Temperature Ratings

• 

See Table A for Temperature combinations

Materials of Construction

• 

Frame - bronze 

 Deflector - brass 

 Screw - brass

• 

Bulb seat - copper 

• 

Spring - nickel alloy 

 Seal - teflon

• 

Bulb - glass with alcohol based solution, 3mm

• 

Cover Plate - Brass

• 

Upper Escutcheon Assembly - carbon steel 

FINISHES AND ACCESSORIES

Sprinkler Finish

   

• 

Factory Bronze

Dome Cover Plates

   

• 

Chrome 

 White Painted 

 Black Painted 

• 

Custom

NOTE:

 

Factory painted cover plates must not be repainted. Non-factory 
applied paint may adversely delay or prevent sprinkler operation 

in the event of a fire.

Wrenches

   •

  1/2” NPT Recessed/Concealed

 

  •

  3/4” NPT Recessed/Concealed

SERIES GL-QR/DC  STANDARD COVERAGE, QUICK RESPONSE 

DOMED CONCEALED PENDENT SPRINKLER 

 K-FACTOR:  2.8, 4.2, 5.6, 8.0 

SERIES GL-QR/DC  STANDARD COVERAGE, QUICK RESPONSE 

DOMED CONC EALED PENDENT SPRINKLER 

K-FACTOR:  2.8, 4.2, 5.6, 8.0 

GFS-104

GFS-104

Отзывы: