HEAT SENSOR 

                   

 

     

   

 

GFE-H Rate of Rise with Fixed Temperature Detector 

Installation Wiring Diagram

 

TYPICAL WIRING DIAGRAM 

Figure 1(a)

 shows the typical wiring diagram of the 

2-wire multiple-station heat detector system.

   

INITIATING

LOOP

EN54  LISTED

COMPATIBLE

CONTROL

PANEL

+
-

FIRST DETECTOR BASE

LAST DETECTOR BASE

EOL
RESISTOR

5

2

5

2

6

1

3

4

6

1

3

4

+

-

+

REMOTE 
INDICATOR

CLASS A OPTIONAL WIRING

NOTE: IF REMOTE INDICATOR IS NOT USED. POLARITY TO DETECTOR MAY BE REVERSED.

-

 

 

Figure 1(b)

 shows the typical wiring diagram of the 

4-wire multiple-station heat detector system. 

 

 

 

WARNING 

TO PREVENT DETECTOR CONTAMINATION AND 
SUBSEQUENT WARRANTY CANCELLATION, THE 
SMOKE DETECTOR MUST REMAIN COVERED UNTIL 
THE AREA IS CLEAN AND DUST FREE. 

INSTALLING THE BASE 

1. To insure proper installation of the detector head to the 

base, all the wires should be properly addressed at 
installation: 
(A) Position all the wires flat against terminals. 
(B) Fasten the wires away from connector terminals. 

2. If you use a jumper wire to connect the poles of 

terminal 2 and 5 when testing the detector loop 
continuity, be sure to remove the jumper wire prior to 
the installation of the detector head. 

3. The end-of-line device shown in fig. 1(a) and 1(b) 

should be compatible with the control unit. The 
end-of-line supervisory relay used should be rated for 
the DC power voltage used. 

4. Open area smoke detectors are intended for mounting 

on a ceiling or a wall in accordance with local 
requirements. 

5. The base of the smoke detector can be mounted 

directly onto an electrical junction box such as an 
octagonal (75mm, 90mm or 100mm), a round (75mm), 
or a square (100mm) box without using any type of 
mechanical adapter. 

INSTALLING THE HEAD 

1. Align the components as shown in Figure 2. 
2. Mate the detector head onto the base and twist 

clockwise to secure it. 

3. 

Do not install the detector head until the area is 

thoroughly cleaned of construction debris, dusts, etc. 
The maximum number of smoke detector installed in 
the same detection zone is typically 30 units. Refer to 
control panel instructions 

 
 
 
 
 
 

 

Fig. 2 Fitting detector head onto base

 

ADJUSTMENT THE RELAY POSITION 
ADJUSTING THE RELAY FOR NO/NC 

The normal condition for the relay is 

normally open

 

(NO). 

1. To adjust the normal condition of the relay to 

normally closed

 (NC), insert a screwdriver into the 

rectangular hole located on the side between the front 
cover and base and rotate to remove the front cover. 

2. Refer to figure 3. There is a jumper head next to the 
relay on the PCB. Remove the jumper head and reinsert 
it in the NC position. 
3. Carefully replace the front cover. 
  Relay contact rating:   

1A@30VDC,  

  0.5A@125VAC

 
 
 
 
 
 

 

TESTING 

1. All remote signaling systems, releasing devices and 

extinguishing systems should be disconnected during 

the test period and reconnected at the conclusion of 

testing. 

2. After energizing the detector head for approximately 

one minute, check to see the indicator red LED 
flashing once every 4-6 seconds. If red LED fails to 
flash, it indicates the non-functioning of the detector or 
faulty wiring. Re-check the wiring or replace the 
detector if necessary. 

3. The detector to be tested should be subject to a flow of 

warm air at a temperature of between 65

°

C and 80

°

C. 

(This requirement can be met by some domestic hair 
dryers). 

Proceed as follows: 
(1). Switch on the warm airflow and check that 

Fig. 3 Schematic of detector structure 
      When front cover is open. 

HEAT SENSOR

RELAY 

POSITION 
SETTING 

LED

 