451905.66.07 · FD 9912
www.gdts.one
English
DHW 300VD+
7.2 Menu structure
Parameter change: The menu is accessed using the
“Menu”
key. In this menu, changes can be made to parameters. The de-
sired menu item is selected with the arrow keys
“UP” “DOWN”
.
The submenu is accessed using the
“OK”
key.
In this submenu, the parameter that is to be changed can be se-
lected (also using the arrow keys). The
“OK”
key is used to se-
lect the marked value, which can then be changed via the arrow
keys. The entry is completed by pressing the
“OK”
key again.
Menu block
Menu item
Parameter
Value
Description
Basic settings
during commissioning:
language
Setting the language
date
Sets the current date
time
Sets the current time
set temperature
Sets the desired domestic hot water temperature
lower
Sets the reduced domestic hot water temperature
settings
time
00:00
Time setting (24 hour time display)
date
DD:MM:YYYY
Date setting (Day:Month:Year)
language
ENGLISH
ENGLISH
FRANCAIS
ITALIANO
POLSKI
Language selection
signal tone
on
off
Setting key tone on / off
backlight
0 % ...
50 %
...100 %
Setting display backlight
factory settings
Factory setting reset
type
DHW 300VD+
Domestic water heat pump DHW 300VD+
with defrost function, additional heat exchanger and ventilation
hot water
set temperature
25 °C ...
45 °C
... 85 °C
Sets the desired domestic hot water set temperature
lower
15 °C ...
25 °C
... 40 °C
Sets the minimum hot water temperature, which should also not be
undershot for the duration of a programmed lower process.
hysteresis
2 K ...
3 K
... 10 K
Sets the switching hysteresis
electrical heater
Mode
Delay
Boost period
Boost set temp.
ECO
AUTO
2 h ...
12 h
...24 h
1 h ...
4 h
... 8 h
25 °C ...
60 °C
... 85 °C
ECO: Only switches in the event of an error and with PV b./t., ther-
mal disinfection on
The electric heater is automatically switched on if the domestic hot
water set temperature is not reached in heat pump operation.
Boost: adjustable time (once, manual switch-on, runs regardless of
the Auto/Eco setting)
Boost: adjustable set temperature
ventilation
level manual
0* /
1
/ 2 / 3 / Auto
Ventilation level if no time program is active/ basic operation
level 1
30 …
60 m³/h
…300 m³/h
Volume flow in level 1
level 2
30 …
90 m³/h
…300 m³/h
Volume flow in level 2
level 3
30 …
120 m³/h
…300 m³/h
Volume flow in level 3
service reset
yes /
no
Confirmation of the maintenance and restart of the time interval
counter
time program
therm. disinfect.
Thermal disinfection
start
00:00
... 23:59
Setting of the start time for a thermal disinfection, duration up to 4
hours, ends at max. 23.59 hours
Days
Mo ...
Su
Sets the day on which thermal disinfection should be activated
Set value
60 °C ...
65 °C
... 85 °C
Sets the set temperature for thermal disinfection.
lower 1
start
00:00
... 23:59
Sets the start time for lowering the domestic hot water set temper-
ature
end
00:00
... 23:59
Sets the end time for lowering the domestic hot water set tempera-
ture