Gira push-button/2-way low voltage Скачать руководство пользователя страница 4

5.2 Commissioning 

Setting the minimum brightness 

The minimum brightness can be set by an electrically skilled person as required. 

DANGER! 
Electrical shock when live parts are touched. 
Electrical shocks can be fatal. 
Use only insulated tools to set the minimum brightness! Cover up live parts in 
the working environment. 

The device is connected as described above and fitted in an appliance box. The frame, central 
plate and control button are not fitted. 

Switch on mains voltage. 

Press the rotary axle to switch on the lighting and turn it left to the minimum brightness. 

Adjust minimum brightness by turning the adjuster (8) (Figure 1). 

According to EN 60669-2-1 (01.2000), lamp brightness should be detectable over the 
whole load area, with darkness at – 10 % rated voltage. 

Switch off the mains voltage. 

Mount the frame and the central plate. Attach the control button. 

Switch on mains voltage again. 

6 Appendix 

6.1 Technical data 

Rated voltage 

AC 230 / 240 V ~ 

Mains frequency 

50 Hz 

Ambient temperature 

+5 ... +25 °C 

Fine-wire fuse 

D 3.15 H 250 

Connected load at 25 °C 

Power specifications including transformer power dissipation. 

Incandescent lamps 

20 ... 500 W 

HV halogen lamps 

20 ... 500 W 

HV-LED lamps 

typical 3 ... 100 W 

Compact fl lamp. 

typical 3 ... 100 W 

Inductive transformers 

20 ... 500 VA 

Operate inductive transformers with at least 85% nominal load. 

32534532 

10499194  I00 

20.12.2013 

4/6 

Dimmer push-button/2-way low voltage 