Gira nurse call system Plus
Short instructions
Power rectifier Plus 5981 00 for installation on DIN top-hat rail
Power rectifier Plus 5998 00 for wall installation
Safety instructions
Installation and mounting of electrical devices may only be
carried out by qualified electricians.
Failure to observe the instructions can result in damage to the
device, fire or other dangers.
Isolate before working on the device or load. Take account of all
circuit breakers supplying dangerous voltage to the device or
load.
Function
Power supply unit with input voltage of 230 V AC +/-15 %.
Output voltage 24 V DC.
The device is designed for 24-hour operation at rated output.
Scope of delivery
•
Order No.: 5981 00, power rectifier Plus with carrier for installa-
tion on DIN top-hat rail.
or
•
Order No.: 5998 00, power rectifier Plus for wall installation.
Installation
The power rectifier Plus must be installed in a dry, dust-free and well
ventilated location.
Order No.: 5981 00 intended for installation on top-hat rail.
Order No.: 5998 00 intended for wall installation.
Device overview
The power rectifier 5998 00 has an LED status display in the device
cover:
The LED lights up green when mains voltage is applied.
Fig.
1: The PCB of the power rectifier
GB
i
Provide circuit breaker!
Connect a circuit breaker type D, max. 16 A upstream from the
power supply unit.
i
Note: read the system operating instructions.
Become familiar with all the possibilities of the device and the
complete call system. Please read the
system operating instruc-
tions
available in various languages on the CD-ROM enclosed
with the ward control centre.
Important! Do not install in patient's rooms!
The device must be securely installed. Access to the device for
skilled electrical personnel must be possible at all times.
Important! Danger of overheating!
With an unfavourable installation location, heat accumulation may
cause device overheating. This may cause damage. Ensure sufficient
air circulation to prevent heat accumulation.
Legend:
Terminals for input voltage 230 V AC
Terminals for output voltage 24 V DC
Micro-fuses: input T 2 A, output T 6.3 A
Status LED: green when mains voltage applied.
Gira
Giersiepen GmbH & Co. KG
Electrical installation
systems
P.O. Box 1220
42461 Radevormwald
Phone +49 (0) 2195 / 602 - 0
Fax
+49 (0) 2195 / 602 - 191
www.gira.com
[email protected]
499266
34/11
499266_EN.fm Seite 1 Sonntag, 28. August 2011 9:40 21