Performing function test

The function test is a manual test of the 
smoke alarm device. 

1. Initiate the function test on the smoke 

alarm device.
After 5 s the signal tone is emitted and 
the ring indicator flashes. 
All other radio-networked smoke alarm 
devices only emit an acoustic alarm 
(after 60 s at the most). 

Radio transmission

Radio transmission occurs on a non-
exclusive transmission path so that 
interference cannot be excluded. Radio 
transmission is 

not

 suitable for security 

purposes (e.g. emergency-stop, emergency 
call). The range of the radio system depends 
on transmitter power, the reception 
characteristic of the receiver, humidity, 
installation height and the building itself.
Examples for material penetration:

Replacing the battery

1. Remove the smoke alarm device from 

the mounting plate or 230 V base.

2. Open the battery cover of the radio 

module and remove the battery.

3. Replace the empty battery with a new 

one of the same time (see technical 
data) and close the battery cover again.

4. Remount the smoke alarm device.
5. Perform a function test.

For "weak battery", the signalling (without 
alarm) behaves as follows:
• 3 short bleeps from the smoke alarm 

triggering the "weak battery" and

• 2 short bleeps from the networked 

smoke alarm.

i

Function test of the smoke alarm 
device

Observe all notes for performing a function 
test of the smoke alarm device Dual Q in 
the installation and operating instructions 
of the smoke alarm device Dual Q. 

i

Delayed signalling of the radio 
module

The radio module checks the reception of 
alarm messages every 60 s.
Therefore, it may take up to 60 s until the 
radio module acknowledges reception. 

Dry material

Penetration

Wood, plaster, 
sheetrock

approx. 90%

Brick, pressboard

approx. 70%

Reinforced concrete

approx. 30%

Metal, metal grids, 
aluminium cladding

approx. 10%

Rain, snow

approx. 0-40%

Remove empty batteries 
immediately and dispose of them 
in an environmentally-friendly 
way. Do not dispose of batteries 
with household waste. Local 
authorities provide information 
about environmentally-sound 
disposal. The end consumer is 
legally required to return used 
batteries in accordance with 
legislative requirements.

Technical data

Warranty

The warranty is provided in accordance with 
statutory requirements via the specialist 
trade.
Please submit or send faulty devices 
postage paid together with an error 
description to your responsible salesperson 
(specialist trade/installation company/
specialist electrical trade).
The salesperson will forward the devices to 
the Gira Service Center.

Power supply:

from battery of the 
radio module

Battery
Type:

2/3 AA lithium

Capacity:

3 V

Transmission frequency: 433.42 MHz, ASK
Transmission range:

100 m (free field)

Ambient temperature:

-5 °C to +50 °C

Protection class:

IP 20

Содержание Dual 2347 00

Страница 1: ...ctrical installation technology possess this knowledge and experience If these minimum requirements are not fulfilled or disregarded there is a risk of personal liability for material damage and injur...

Страница 2: ...e transformer for eNet The radio range can be extended with repeater mode in the radio module Up to 40 smoke alarm devices can be networked The radio module is downward compatible which means it can a...

Страница 3: ...psed Alternatively you can briefly press the Prog button Radio networked group Radio modules can only communicate with each other within a group A radio networked group must be set up for this purpose...

Страница 4: ...e programming mode on the radio module of any smoke alarm device Dual VdS 2 Activate programming mode on the radio module of the smoke alarm device Dual Q 3 Press the function button of the smoke alar...

Страница 5: ...dule is automatically taught into the eNet radio blind actuator Mini 5 Press the Prog button on the eNet radio blind actuator Mini approx 4 s 6 Activate programming mode on the remote control 2 gang 7...

Страница 6: ...g mode 2 Release the Prog button 3 Repress the Prog button of the radio module approx 10 s A brief signal tone is emitted after approx 4 s After approx 10 s a longer signal tone is emitted and the pro...

Страница 7: ...the battery cover again 4 Remount the smoke alarm device 5 Perform a function test For weak battery the signalling without alarm behaves as follows 3 short bleeps from the smoke alarm triggering the...

Страница 8: ...scription to your responsible salesperson specialist trade installation company specialist electrical trade The salesperson will forward the devices to the Gira Service Center Power supply from batter...

Отзывы: