Technical data
Best. Nr. 1060 00
Page 18 of 136
3 Technical data
Type of protection:
IP 20
Safety class:
III
Mark of approval:
KNX / EIB / VDE
Ambient temperature:
-5 °C ... +45 °C
Storage / transport temperature:
-25 °C ... +70 °C
(Storage above + 45 °C reduces the lifetime)
Mounting position:
optional (screw terminals preferably on top)
Minimum distances:
none
Type of fastening:
Snap-fastening on DIN rail in closed cabinets (e.g. small
distributions, etc.) / KNX / EIB data rail not required.
KNX / EIB supply
Voltage:
21…32 V DC SELV
Power consumption:
typically 150 mW
Connection:
standard KNX/EIB bus connection terminal
External supply
Voltage:
110...240 V AC +10 % / -15 %, 50/60 Hz
Power consumption:
max. 6 W
Connection:
with screw terminals:
0,5…4 mm² solid and stranded wire without ferrule
0,5…2,5 mm² stranded wire with ferrule
Max. tightening torque: 0.8 Nm
Total power loss:
max. 3 W
Response to bus voltage failure:
depending on parameterization
(cf. chapter 4. "Software description")
Response to bus voltage failure
As per parameterization, the device can report the supply voltage
failure to the bus. Afterwards, the device will completely shut
down.
Response to bus voltage return:
depending on parameterization
(cf. chapter 4. "Software description")
Response to mains voltage return:
The device will briefly initialize ("
" display) and is then ready
for operation. As per parameterization, the device can report the
return of supply voltage to the bus.
The brightness of a DALI group depends on the parameterization
(cf. Chapter 4. “Software description”).