"DALI Gateway C00CX2 EN / C00CX4 EN" software
Functional description
Best. Nr. 1060 00
Page 83 of 136
Created scenes can be deleted at any time by selecting a scene and executing the “Delete” command
in the context menu.
Each scene can be assigned a name. The scene must be selected and opened via the “Rename”
command in the context menu. It is recommended to assign each scene a unique name (e.g. “Lecture
desk”, “Meeting large”, etc.). The name may not exceed 28 characters and may include alphanumerical
as well as special characters.
For better orientation and differentiation of the individual scenes, the name will only be shown in the
plug-in. A scene name can also be edited in the parameter configuration of a scene via the “Name”
parameter.
The scene brightness values are recalled or stored via a separate scene extension object affecting
several channels by means of extension telegrams. The data point type of the extension object makes
it possible to control each scene separately via their fixed scene number (1...16). Optionally, each
scene recall can also be delayed.
A scene recall overrides a set brightness value via the “Brightness value” object as well as a switching
or dimming operation via the “Switching”, “Switching central function” and “Dimming” objects of a
group. A Staircase timer function will also be overridden by a scene recall. The priority of the scene
function to the disable or forced-control position functions of a group can be parameterized for each
scene. That makes it possible to have a scene recall override a disable or forced-control position
function. Alternatively, a scene can have a lower priority preventing disable or forced-control position
functions to be overridden by a scene recall.
A function overridden by a scene recall will be re-executed if the function has been updated via the
KNX/EIB.
Time functions
Object
"Switching"
additional function
Behaviour
- bus voltage failure
- bus voltage return
- ETS programming
*
Object
"Brightness value
feedback"
Blinking
*
Group
* = optional parameterization
Object
"Central function"
Polarity of
central object
*
Object
"staircase timer
function start/stop"
Object
"Extension unit"
Scene
control
recall
storing **
*
*
Staircase timer
function
(timing)
*
Object
"Brightness value"
Object
"Dimming"
automatic
shutoff function
Scene priority
lower
higher
Soft-ON / OFF
*
Dimming speed /
Dimming behaviour
*
Verzögerung nach
Busspannungswiederkehr
zyklisches Senden
Object
"Disable" / "Forced-control"
** = Basically, no new scene value will
be stored if a disable or forced-control
position is active!
Object
"Switching
feedback"
*
*
*
Fig. 32: Functional diagram of the scene function