"DALI Gateway C00CX2 EN / C00CX4 EN" software
Functional description
Best. Nr. 1060 00
Page 74 of 136
Figure 23 shows the functional diagram of the Soft functions. The Soft functions will also affect the
switching edges of the Staircase timer function.
Time functions
Object
"Switching"
additional function
Behaviour
- bus voltage failure
- bus voltage return
- ETS programming
*
Object
"Brightness value
feedback"
Blinking
*
Group
* = optional parameterization
Object
"Central function"
Polarity of
central object
*
Object
"staircase timer
function start/stop"
Object
"Extension unit"
Scene
control
recall
storing **
*
*
*
Staircase timer
function
(timing)
*
*
Object
"Brightness value"
Object
"Dimming"
automatic
shutoff function
Scene priority
lower
higher
Soft-ON / OFF
*
Dimming speed /
Dimming behaviour
*
Verzögerung nach
Busspannungswiederkehr
zyklisches Senden
Object
"Disable" / "Forced-control"
** = Basically, no new scene value will
be stored if a disable or forced-control
position is active!
Object
"Switching
feedback"
*
*
Fig. 23: Functional diagram of the Soft functions
A DALI group that has been disabled via the bus may also blink depending on the parameterization.
An ON and OFF blinking will not be dimmed with the Soft functions.
Setting and enabling the Soft-ON function
The Soft-ON function can be set separately for each group in the plug-in of the DALI Gateway.
Set the “Soft-ON function ?” parameter in the “Groups - [x] group name – Switch-on/ switch-off
behaviour" parameter node to “Yes”.
The Soft-ON function is now enabled. The parameter for the dimming time of the Soft-ON function
becomes visible.
Configure the “Time for Soft-ON (0...100 %)” parameter in the "Groups - [x] group name – switch-on-
/switch-off behaviour" to the required dimming time.